Installation Manual
92 Rinnai I-Series Condensing Boiler Solo Manual
Parameter
Number
Seng Descripon
Selecon
A b C d
40
Linked Operaon Between CH Pump 1 and 2
No
Yes (Linked
Together)
This parameter enables linked operaon
between the CH Pump 1 and 2. For example,
when T/T 1 is acve, both pump 1 and 2 are ON.
The T/T wire must be connected to the T/T1
connecon.
When it is desired to ulize DHW Recirculaon
via DIP switch 3, this parameter will not be
available. The DIP switch must be in the OFF
(default) posion for this parameter to be
enabled.
This seng is primarily for an applicaon that
requires two pumps for one zone, such as in use
with an injecon loop or similar system.
41
Linked Operaon Between Main Boiler Pump
and CH Pump 1
No
Yes (Linked
Together)
This parameter is only in use when DIP switch 2
is in the ON posion.
This enables the linked operaon between the
main boiler pump and CH pump 1. For example,
when the main pump is on, pump 1 is also on.
When DIP switch 2 is in the OFF posion, the
pumps are automacally linked.
42
Main Pump Runs When the Target Temperature
is Achieved
Connuously Intervals
This selects the mode of the main pump running
when the target setpoint is achieved. This
seng is for whether running on intervals to
reduce pump operaon or connuously running
to reduce wait me to re-re. Intervals are 10
minutes ON and 30 minutes OFF.
43
External Pump Runs When the Setpoint
Temperature is Achieved
Same as Main
Pump
Does Not
Run
This selects the mode of the external pump(s)
running when the target setpoint is achieved.
This seng is for whether stopping the external
pump from running to reduce pump operaon
me or it operates the same as the main pump
to enable remaining heat from the heat
exchanger to be delivered to the system.
44
External Pump Runs When Freeze Protecon is
in Operaon
Does Not Run Same as Main
Pump
(if selected,
hydraulic
separaon is
needed)
This selects how the external pump operates
when freeze protecon is in operaon. This
selects whether the pump will run to reduce the
pumps operaon me or operang the same as
the main pump to enable the boiler to deliver
the remaining heat to the system. The
temperature water being delivered to the
system may not be as warm as desired with this
seng ON.