Installation Manual

Rinnai I-Series Condensing Boiler Solo Manual 97
Curve 4 is a custom curve based on the target setpoint temperature of the boiler the customer selects.
The maximum temperature is the target temperature. The minimum temperature is 36°F (20°C) lower
than the target temperature with a minimum of 86°F (30°C). See example curves below.
Curve 4
To select the desired reset curve, access the parameters (as shown in secon “12.4 Parameter
Sengs”) and select parameter 01. Then, select the desired curve.