Installation Guide
50 Rinnai I-Series Condensing Boiler Solo Manual
• Purge the heang system to remove all
debris and air. Debris and air in the lines
will damage the boiler.
• When removing the plasc sealing caps
from the boiler connecons, water may
come out of the boiler due to live re
tesng during manufacturing.
• The boiler, when used in connecon with
a refrigeraon system, must be installed
so the chilled medium is piped in parallel
with the boiler with appropriate valves
to prevent the chilled medium from
entering the boiler.
• The boiler piping system of a hot water
boiler connected to heang coils located
in air handling units where they may be
exposed to refrigerated air circulaon
must be equipped with ow control
valves or other automac means to
prevent gravity circulaon of the boiler
water during the cooling cycle.
• Some installaons with mulple zone
valves may require a dierenal bypass,
which will prevent excessively high ow
rates through a single zone when the
other zone valves are closed.
To connect the water supply, follow the
instrucons below.
For standard installaons, refer to the “Piping
Diagram for Basic Central Heang
Installaon” in this chapter.
Plumb the heang return line to the
heang return connecon on the
boom of the boiler.
CAUTION
• Guidelines
• Instrucons
• Common CH Components
• Piping Diagram for a Basic CH System
(Without Hydraulic Separaon)
• Piping Diagram for a Basic CH System
(With Hydraulic Separaon)
• Hydraulic Separaon
• Connect the Pressure Relief Valves
• Connect the Condensate Drain Line
• Condensate Pump Safety Switch
Wiring
Topics in this secon
7
The boiler may not be installed directly to
a heang system where polybutylene or
other oxygen permeable piping is used.
Water connecons to the boiler should
follow all state and local plumbing codes.
IMPORTANT
• It is required to include an air separator
on the central heang supply of the
system.
• System piping should be insulated when
freezing is a potenal concern.
• All piping must comply with local, state,
naonal or ASME code as appropriate.
Heang Return Connecon