Installation Manual
Rinnai I-Series Condensing Boiler Solo Manual 17
Contaminant Maximum Level
Total Hardness Up to 200 mg/L
Aluminum * Up to 0.2 mg/L
Chlorides * Up to 250 mg/L
Copper * Up to 1.0 mg/L
Dissolved Carbon Dioxide
(CO2)
Up to 15.0 mg/L
Iron * Up to 0.3 mg/L
Manganese * Up to 0.05 mg/L
pH * 6.5 to 8.5
TDS (Total Dissolved
Solids) *
Up to 500 mg/L
Zinc * Up to 5 mg/L
Consideraon of care for your boiler should
include evaluaon of water quality.
• The water must be potable, free of
corrosive chemicals, sand, dirt, or other
contaminants.
• It is up to the installer to ensure the
water does not contain corrosive
chemicals or elements that can aect or
damage the boiler.
• Water that contains chemicals
exceeding the levels below can damage
the boiler.
* Source: Part 143 Naonal Secondary Drinking Water Regulaons
When choosing an installaon locaon, you
must ensure that clearances will be met and
that the vent length will be within required
limits. Consider the installaon
environment, water quality, and need for
freeze protecon. Requirements for the gas
line, water lines, electrical connecon, and
condensate disposal can be found in their
respecve installaon secons in this
manual.
This secon provides informaon on the
importance of water quality to the Rinnai
Condensing Boiler. The informaon is
intended to serve as general guidelines only
and is not a complete list of water quality
guidelines.
• Unsuitable heang system water can
cause the formaon of scale or sludge,
which aects system eciency. It can
also cause corrosion and reduce life of
the heat exchanger.
• Never use water that has been treated
by a reverse osmosis, deionized, or
dislled water to soen the water to
ll the heang system.
• Oxygen permeable or rubber tubing is
not permied in the heang system
unless it is separated from the boiler by
a plate heat exchanger.
• Thoroughly ush the system prior to
lling. While ushing, isolate the boiler.
• Do not introduce any system cleaner
into the boiler. Flush the system
thoroughly to remove all system
cleaner before lling the boiler with
water.
• When freeze protecon of the heang
system is desired, only use Rinnai-
approved anfreezes. The allowed
maximum concentraon is 40%.
• Reference secon “14.1 Approved
Cleaners, Inhibitors and Anfreezes” in
the Appendix for an approved list of
system cleaners, inhibitors, and
anfreezes.
IMPORTANT
Replacement of components due to
water quality damage is not covered by
the warranty.