Installation Manual

Rinnai I-Series Condensing Boiler Solo Manual 17
Contaminant Maximum Level
Total Hardness Up to 200 mg/L
Aluminum * Up to 0.2 mg/L
Chlorides * Up to 250 mg/L
Copper * Up to 1.0 mg/L
Dissolved Carbon Dioxide
(CO2)
Up to 15.0 mg/L
Iron * Up to 0.3 mg/L
Manganese * Up to 0.05 mg/L
pH * 6.5 to 8.5
TDS (Total Dissolved
Solids) *
Up to 500 mg/L
Zinc * Up to 5 mg/L
Consideraon of care for your boiler should
include evaluaon of water quality.
The water must be potable, free of
corrosive chemicals, sand, dirt, or other
contaminants.
It is up to the installer to ensure the
water does not contain corrosive
chemicals or elements that can aect or
damage the boiler.
Water that contains chemicals
exceeding the levels below can damage
the boiler.
* Source: Part 143 Naonal Secondary Drinking Water Regulaons
When choosing an installaon locaon, you
must ensure that clearances will be met and
that the vent length will be within required
limits. Consider the installaon
environment, water quality, and need for
freeze protecon. Requirements for the gas
line, water lines, electrical connecon, and
condensate disposal can be found in their
respecve installaon secons in this
manual.
This secon provides informaon on the
importance of water quality to the Rinnai
Condensing Boiler. The informaon is
intended to serve as general guidelines only
and is not a complete list of water quality
guidelines.
Unsuitable heang system water can
cause the formaon of scale or sludge,
which aects system eciency. It can
also cause corrosion and reduce life of
the heat exchanger.
Never use water that has been treated
by a reverse osmosis, deionized, or
dislled water to soen the water to
ll the heang system.
Oxygen permeable or rubber tubing is
not permied in the heang system
unless it is separated from the boiler by
a plate heat exchanger.
Thoroughly ush the system prior to
lling. While ushing, isolate the boiler.
Do not introduce any system cleaner
into the boiler. Flush the system
thoroughly to remove all system
cleaner before lling the boiler with
water.
When freeze protecon of the heang
system is desired, only use Rinnai-
approved anfreezes. The allowed
maximum concentraon is 40%.
Reference secon 14.1 Approved
Cleaners, Inhibitors and Anfreezesin
the Appendix for an approved list of
system cleaners, inhibitors, and
anfreezes.
IMPORTANT
Replacement of components due to
water quality damage is not covered by
the warranty.