20 Rinnai I-Series Condensing Combi Boiler User’s Informaon Manual
The CH target setpoint temperature can be set
in 2°F (1°C) increments between 104°F-180°F
(40°C-82°C).
Factory Default: 140°F
Target Setpoint Temperatures
Type of Heat
Emier
Typical
Minimum
Supply
Temperature
Typical
Maximum
Supply
Temperature
Hydronic Air
Handler
120 - 140°F 140 - 180°F
Unit Heater 130 - 140°F 160 - 180°F
Base Board
Convectors
100* - 140°F 140 - 180°F
Cast Iron/
Panel
Radiator
90* - 120°F 140 - 180°F
Undermount
Radiant
100* - 120°F 120 - 150°F
Below are some typical target setpoint
temperatures for various heat emiers. These
are basic guidelines; thus, check with the
emier manufacturer or consult your heang
design engineer.
Only adjust the target setpoint
temperature of the system by consulng
with the installer of the system or other
qualied professional. If the target
setpoint temperature is adjusted too high
for the heat emiers in use, property
damage may occur.
WARNING
*Other hydronic components may be necessary
to achieve minimum supply temperatures.