I Series Combi Installation Manual

Rinnai I-Series Condensing Boiler Combi Manual 21
I-Series boilers can be installed in
direct vent or non-direct vent
applicaons.
When installed as Direct Vent, refer to
the following secon for a complete
list of approved vent manufacturers
and products: “5.5.1 Direct Vent:
Approved Vent Manufacturers and
Products.”
When installed as Non-Direct Vent
(Room Air), the vent must be Category
IV and of a type listed by a naonal
recognized tesng agency.
Exhaust must be directly vented to
the outside. Combuson air can be
provided from outside (Direct Vent) or
from room air (Non-Direct Vent).
If using room air (non-direct vent) for
combuson, ensure the required
volume of indoor air is available
according to the Naonal Fuel Gas
Code, ANSI Z223.1/NFPA 54.
Avoid dips or sags in horizontal vent
runs by installing supports per the
vent manufacturer’s instrucons.
Support horizontal vent runs every 4
 (1.2 m) and all vercal vent runs
every 6  (1.83 m) or as per vent
manufacturer’s instrucons or local
code requirements.
Topics in this secon
Guidelines
Venng Installaon Sequence
Terminaon Consideraons
PVC Venng Safety Switch
Venng Opons
5
Venng should be as direct as possible
with a minimum number of pipe ngs.
For manufactured vent systems, vent
connecons must be rmly pressed
together so that the connecons form an
air ght seal. Follow the venng
manufacturer’s instrucons.
Refer to the Schedule 40 PVC/CPVC
manufacturer for appropriate ngs,
solvents or joining methods.
If venng reassembly is needed, follow
the steps for installing the venng in the
following secons. Make certain that the
vent piping and seals are not damaged.
Only use sealants, primers, or glues that
are approved for the vent material in use.
Refer to the instrucons of the vent
system manufacturer for component
assembly instrucons.
If the vent system is to be enclosed, it is
suggested that the design of the enclosure
shall permit inspecon of the vent system.
The design of such enclosure shall be
deemed acceptable by the installer or the
local inspector.
Any issues resulng from improper vent
installaon will not be covered by
warranty.
DO NOT use cellular core PVC/CPVC.
DO NOT use Radel, ABS, or galvanized
material to vent this appliance.
DO NOT cover non-metallic vent pipe
and ngs with thermal insulaon.
DO NOT combine vent components
from dierent manufacturers.
DO NOT reduce the vent diameter. Vent
diameter cannot be less than 2 in.
DO NOT connect the venng system
with an exisng vent or chimney.
DO NOT common vent with the vent
pipe of any other manufacturer’s boiler
or appliance.
WARNING