I Series Combi Installation Manual
Rinnai I-Series Condensing Boiler Combi Manual 97
When the recirculaon logic starts, the pump will operate as described below:
When the DHW return water temperature reaches approximately 6°F (3°C) below the
DHW set point temperature, power to the pump will be disconnued from the PC Board.
Aer the o interval me of the boiler has passed, the pump will turn on again.
If the boiler does not detect ow from the pump during the DHW recirculaon on mes,
an E631 diagnosc code will display on the controller.
Timer Connects to T/T 2
IMPORTANT
The target ow rate for DHW recirculaon is from 1.3 GPM (5 L/min) to 4 GPM (15 L/min). If the
ow rate is less than 0.8 GPM (3 L/min), the DHW recirculaon pump will operate and an E631
diagnosc code will display on the controller. If the DHW recirculaon pump ow rate drops to
less than 0.4 GPM (1.5 L/min), the DHW recirculaon pump will stop and an E631 diagnosc
code will display on the controller. The proper pump size needs to be selected for the pressure
drop through the recirculaon loop (maximum current: 2 Amps).
DHW Recirculaon Pump
Connect to “DHW_Pump
Terminal” (label on PC Board)