Installation Guide

Rinnai I-Series Condensing Boiler Combi Manual 101
140
Heat Exchanger Overheat
Overheat switch is tripped.
Measure the resistance of the Overheat
Switch.*
Check the heat exchanger surface for hot
spots which may indicate blockage due
to scale buildup.
Ensure the boiler pump is not locked up.
Ensure that all of the valves in the CH
circuit are open.
Ensure the boiler and CH circuit does not
have a freezing condion.
The surface of the heat exchanger may
turn to a black color as stainless steel is
tempered even in normal condions.
This does not indicate an abnormal
condion.
Check for damage on the exhaust, seal,
and venng.
150
Venturi Control
Venturi operaon error.
Ensure the venturi motor is operang
correctly.*
Replace the gas valve assembly.
161
High Outgoing Temperature
Safety shutdown because DHW outgoing
temperature is too hot.
Check sensor wiring for damage of
outgoing thermistor.
Measure resistance of outgoing
thermistor.*
Ensure the gas valve has no damage and
the orice is installed correctly.
Replace the gas valve assembly.
170
Venturi Blockage
Check the venturi and silencer for
blockage.
Before reseng this error, check if the
condensate drain is block and if the
venng is connected properly.
190
Electrical Grounding
Secondary circuit ground fault.
Check all electrical components for
electrical short.
250
Condensate Pump (Accessory)
Boiler will operate for 60 seconds.
Conrm wire connecons and
harnesses are good.
Ensure the condensate reservoir is
empty and condensate pump is
operaonal.
341
Inlet Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
353
Supply Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.
321
Outgoing Thermistor
Check sensor wiring for damage.
Clean sensor of any scale buildup
present.
Measure the resistance of the sensor.
Replace if necessary.
331
Heat Exchanger Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
310
Freeze Protecon Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
380 Exhaust Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.
363
Return Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
393
Outdoor Thermistor
Ensure that DIP switch 1 is set to the
appropriate posion.
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
400
Pressure Sensor
Check sensor wiring for damage.
Measure the voltage of the sensor.
Replace if necessary.
* See Electrical Diagnoscson Technical Data Sheet located on inside front cover of boiler.