Installation Guide
Rinnai I-Series Condensing Boiler Combi Manual 107
ANNUALLY
Vent System • Inspect for blockages or damage.
• Inspect vent screen or room air lter (if using) for debris and blockages.
Clean if needed.
Fan and Motors Clean dust and dirt from fan and motor (motors are permanently lubricated
and do not require lubricaon).
Controller Clean by using a so, damp cloth. Do not use solvents.
Pressure Conrm the pressure is within the proper range (between 17-26 PSI). If the
pressure is lower than the specied range, add water unl in the proper range.
Pressure Relief
Valve
Operate the pressure relief valve manually once a year. In doing so, it will be
necessary to take precauons with regard to the discharge of potenally
scalding hot water under pressure. Ensure discharge has a safe place to ow.
Contact with your body or other property may cause damage or harm.
Heang System
Filter
Clean annually. Be sure to close the shut o valves under the boiler. Aer
cleaning and installing the lter, purge the air.
DHW Filter If the ow volume of DHW is geng less, clean the lter at the DHW inlet. Be
sure to close the shut o valves on the DHW pipes under the boiler.
Expansion Tank Perform annual checks as recommended by the manufacturer to ensure proper
operaon.
Condensaon
Trap
Check if the trap contains sediment. To remove sediment, unplug the boom of
the condensate trap. Remove the sediment, and then return the plug. Do not
use a wrench to ghten the condensate drain as this could cause the
connecon to break.
Condensaon
Drain
• Conrm the condensaon drain line is not blocked or clocked.
• Ensure the condensaon drain pump (if ulized) is working correctly.
Flushing DHW
Heat Exchanger
Flushing for DHW (plate heat exchanger). When LC code appears, the boiler
detects lime scale accumulaon. Once the ushing done, the LC code will
disappear automacally. If the boiler is installed in hard water area, Rinnai
recommends periodically ushing.
Draining Water When the system will be shutdown for a long period of me (seasonal
shutdown), close the shuto valves below the boiler and drain the boiler to
protect it from potenal freeze damage.
Tesng the pressure relief valve should only be
performed by a licensed professional. Water
discharged from the pressure relief valve could cause severe burns
instantly or death from scalds.
WARNING