Installation Guide
88 Rinnai I-Series Condensing Boiler Combi Manual
46
The Dierenal Temperature from Ceasing Fire
to Firing Again
Normal Quick
How much temperature drop is permied by
the supply water thermistor before the boiler
will re again.
When selecng "Quick", the boiler will re more
frequently and achieve more temperature
control.
CH Seng Temperature
Temperature Drop
168-182°F (75-82°C)
27°F (15°C) 15°F (8°C)
104-166°F (40-74°C)
15°F (8°C) 9°F (5°C)
47
The Time Which the Boiler is not Allowed to Fire
Again for CH
Normal
(3 Minutes)
Quick
(10 Seconds)
This selects the me which the boiler will not be
able to re again for CH aer the burner has
shutdown. This seng is to prevent frequent
ON/OFF operaon.
49
Will the boiler shut down on a high return water
temperature
Yes No
This seng is for whether the boiler will shut
down at high return water temperatures. This is
to decrease the o cycle me even though the
return water temperature is warm.
60
Not Available
Not Available
A0
Gas Type
Natural
Gas
Liquid
Propane
For selecng gas type when conducng gas
conversion.
A1
Not Available
Not Available
A2
Vent Material Used
PVC
Material
other than
PVC:
CPVC/PP/
Other
This selects the venng material used. The
boiler is set from the factory to be installed in a
PVC venng system. If CPVC, PP, or other
approved venng is used, this may be adjusted.
See secon “5.4 PVC Venng Safety Switch” for
more informaon.
45
Freeze Protecon Level
Default
When Boiler
is Installed in
a Warm
Room
This selects the freeze protecon level.
Selecng “B” will prevent the boiler from
operang in freeze protecon mode more than
believed necessary.
Parameter
Number
Seng Descripon
Selecon
A b C d
44
External Pump Runs When Freeze Protecon is
in Operaon
Does Not
Run
Same as Main
Pump
This selects how the external pump operates
when freeze protecon is in operaon. This se-
lects whether the pump will run to reduce the
pumps operaon me or operang the same as
the main pump to enable the boiler to deliver
the remaining heat to the system. The tempera-
ture water being delivered to the system may
not be as warm as desired with this seng ON.
Note: If “Same as Main Pump” is selected, hy-
draulic separaon is needed.