Installation Guide
Rinnai I-Series Condensing Boiler Combi Manual 95
Parameter
Number
Funcon/Descripon
Selecon
A
(Default)
b
12
DHW Recirculaon piping setup
Crossover
Valve
Dedicated
Return
This parameter is available when Dip SW 3 is in the ON posion.
This sets the DHW recirculaon piping mode, which controls the circula-
on logic. Ensure this corresponds to the DHW recirculaon piping.
13
DHW Recirculaon with mer relay input
Yes No
This parameter is available when Dip SW 3 is in the ON posion.
This enables an external mer to also control the ming for DWH recir-
culaon to more directly correspond to the customers needs.
14
CH temperature limitaon during Simultaneous Operaon
Yes No
This parameter is available when Dip SW 3 or 4 are in the ON posion.
This enables the CH temperature seng to be limited during simultane-
ous DHW and CH operaon. This can prevent unintenonally supplying
high temperature DHW to low temperature CH applicaons.
During simultaneous operaon, supply temperature may be up to 180°F.
When selecng "NO" limitaon, ensure that the CH system and heang
applicaon is designed for this temperature.
15
3 Way Valve Posion During Simultaneous Operaon
Normal Addional CH
This parameter is available when DIP switch 3 or 4 is in the ON posion.
This adjusts the 3 Way Valve posion to open the CH side more for when
the ow of the CH side is reduced due to DHW demand. This may restrict
the DHW capacity.
To enable recirculaon:
1. Remove the boiler’s front panel by removing the four screws that secure the panel.
2. Adjust DIP switch 3 to the ON posion.
3. Select the appropriate parameter sengs from Parameters 12-15 for the system.
See Parameter Seng instrucons for instrucons on adjusng parameters.
PC Board
DIP Switches
Push the PCB
Buon Switch
4 (Red buon)
to move to
Seng Mode.
ON