Specification

CONDENSING WALL-MOUNTED, GAS-FIRED HEAT-ONLY BOILER
Models i060S, i090S, i120S, i150S
Appliance Wall-Mounted, Gas-Fired Heat-Only Boiler
Installaon
Indoor
Gas Type Natural Gas (or Propane with included eld conversion kit)
Standard
Features
Outdoor Reset Control System with Sensor
Modulang Stainless Steel Mesh Burner
Stainless Steel Water Tube Heat Exchanger
Direct Vent Sealed Combuson
Approved for Room Air and Closet Installaons
Included
with Boiler
Purchase
Propane Field Conversion Kit
Wall Mounng Bracket
CH Pressure Relief Valve (30 PSI)
Outdoor Temperature Sensor
Integrated Vent Adapter for 2 in. PVC, PP and
3 in. x 5 in. Concentric Venng
Documentaon: Installaon and Operaon Manual,
User Manual, and Technical Data Sheet
Accessories Primary-Secondary Heang Kit (PN: 807000213),
Condensate Neutralizer (PN: 804000074), and ScaleCuer
(PN: 103000038)
Venng
Opons
Direct Vent (Concentric and Twin Pipe)
Room Air
Ubbink Flex Vent
Materials: Polypropylene, Stainless Steel, PVC, CPVC
Refer to the Rinnai I-Series Boiler Installaon and
Operaon Manualfor approved venng.
Measurements: in. (mm)
Maximum Equivalent Vent Lengths
Concentric, Twin Pipe, and Room Air:
Vent Sizes
2 in. PVC
2 in. (60 mm) PP
2 in. x 4 in. Concentric
3 in. PVC
3 in. (80 mm) PP
3 in. x 5 in. Concentric
Maximum
Vent Lengths
65  (20 m) 150  (46 m)
Ubbink Flex:
Vent Sizes 2 in. PP
Maximum Vent Lengths 50  (15 m)
45° elbow equivalent to 3  (1 m). 90° elbow equivalent to 6  (2 m).