Flue Installation Manual Rinnai FFU coaxial flue system, suitable for use with the following Rinnai internal continuous flow water heater models: INFINITY 26i HD 200i – – REU-VR2632FFUG REU-VRM2632FFUC These components shall be installed in accordance with: ! " # $ % & $ # $ These components ' ( $ ) $ $ ' ) $ (* + $ . / Quality ISO 9001 Part No.
BEFORE PROCEEDING WITH INSTALLING A FF COAXIAL FLUE SYSTEM, READ THIS MANUAL THOROUGHLY TO GAIN A FULL UNDERSTANDING OF THE INSTALLATION REQUIREMENTS.
INSTALLATION GENERAL This flue must be installed by an authorised person. The Installation must conform to local regulations. Installation must comply with the instructions supplied by Rinnai. Service and removal must be carried out by an authorised person. TABLE OF CONTENTS CERTIFICATION ....................................................................................... 1 GENERAL .................................................................................................. 1 FF FLUEING OPTIONS ...
FF FLUEING OPTIONS FFSBEND FFWPLATE or FFWSEAL (Optional) FFWPLATE or FFWSEAL (Optional) FFSBEND 127mm Hole DIRECT HORIZONTAL (FIG. 1) 127mm Hole 2° fall to terminal 2° fall to terminal FFWPLATE FFWPLATE FFWALLTERM Drain Tube Cap FFWALLTERM Drain Tube Cap 45 minimum FFPIPE1000 VERTICAL (FIG. 3) A vertical installation that consists of flue pipe(s) (FFPIPE1000) and a roof terminal (FFROOFCOWL). See page 5 for details. FFWALLTERM VERTICAL / HORIZONTAL (FIG. 4) 2° fall to terminal Fig.
GENERAL INSTALLATION METHODS Lubricating Components A container of "O ring" grease is provided with the flue terminal components (FFWALLTERM and FFROOFCOWL). To ease assembly, lubricate the “O” ring on the inner pipes of each flue component prior to assembly. Use only a silicone based "O" ring seal lubricant. DO NOT use petroleum based lubricants such as petroleum jelly, as such products may cause deterioration.
DIRECT HORIZONTAL FLUE The Rinnai water heater 'direct' flueing components (FFSBEND, FFWALLTERM, FFWSEAL and FFWPLATE) must be used for this purpose. Installation method 1. Mount the water heater in an appropriate location ensuring that there is enough space to install the flue assembly and pipe work. Also ensure that positioning of the flue terminal complies with the requirements of AS/NZS 5601 see (Fig.6.2 on page 9). Ø127 Wall penetration FFSBEND 3.
VERTICAL FLUE This option can be used when the water heater is to be flued vertically through the roof. The Rinnai water heater 'Vertical Flueing Components' (FFROOFCOWL and FFPIPE1000) with extension pieces (FFPIPE1000) and optional roof seal (FFSEAL) must be used for this purpose. With vertical flue systems the condensate drain pipe will require connection if the total length of the flue system exceeds 2 metres. Refer to the section “CONDENSATE DRAIN” on page 6 for details.
CONDENSATE DRAIN The condensate trap and associated drain connection are integral with the appliance flue spigot. The condensate trap collects any condensate from the flue system, thereby preventing condensate from entering the water heater and causing damage. A condensate drain tube kit is supplied with the terminals (FFWALLTERM and FFROOFCOWL) and will require connection to the condensate drain connection in flue systems where the total length exceeds 1.
CONDENSATE DRAIN Installation Method (a) The drain line MUST NOT discharge onto electrical connections, earth stakes, copper pipes, concrete paths or into a pond. (b) The point of discharge from each drain line shall be located so that the release of condensate does not cause a nuisance, is readily discernible and incurs no risk of damage to the building. In view of (a) and (b), suitable points of discharge are deemed to be drains, sewers or pits.
DIMENSIONS 165 64.5 85 5 176 66 80 85 114 FFBEND (2x 45° Bends) 15 80 15 15 85 FFSBEND 92 5 5 166 130 66 64.
CLEARANCES Flue terminal Fan assisted flue appliance only Ref. Gas meter Electricity meter or fuse box Mechanical air inlet Min. clearances (mm) Natural draft Fan assisted Item Below eaves, balconies and other projections: a Appliances up to 50 MJ/h input 300 200 Appliances over 50 MJ/h input 500 300 b From the ground, above a balcony or other surface * 300 300 c 500 300 d Front a return wall or external corner * From a gas meter (M) (see 5.11.5.
CONTACT INFORMATION Australia Pty. Ltd. Internet: www.rinnai.com.au E-mail: enquiry@rinnai.com.au ABN 74 005 138 769 Head Office National Help Lines 10-11 Walker Street, Braeside, Victoria 3195 P.O. Box 460 Tel: (03) 9271 6625 Fax: (03) 9271 6622 Sales & Service Tel: 1300 555 545* Fax: 1300 555 655* *Cost of a local call Higher from mobile or public phones.