Installation Guide

Rinnai Australia 25 ES Flue Installation Manual
CONNECTING CONDENSATE DRAIN TUBE TO HEATER
1. Condensate trap “ESCONDK”.
2. Carefully mark and drill a 16 diameter mm hole through both the heat
shield panel and appliance back panel. DO NOT allow the drill to penetrate
further than 10 mm past the back panel as damage to the heat exchanger
or internal components will occur.
To insert the condensate drain hose in the appliance drill through
both the raised heat shield and the heater back panel. A 16 mm
diameter hole is required for the correct clearance with the
condensate drain hose supplied.
DO
NOT allow the drill to penetrate further than 10mm past the
back panel as damage to the internal components such as the
heat exchanger will occur.
UNDER NO CIRCUMSTANCES MUST THE APPLIANCE BE OPERATED WITH
A DAMAGED HEAT EXCHANGER
All vertical measurements are from floor level.
* The horizontal measurements are taken from the edge of the raised back panel.
3. Feed approximately 60mm of the free end of the drain tube through the drilled holes created in step 2. above.
Ensure that any condensation can drain into the condensation tray of the heater.
DO NOT allow any portion of the drain tube to come into contact with any part of the heat
exchanger.
DO
NOT kink, crimp or sharply bend any portion of the condensate drain tube.
4. Secure the drain tube to the rear of the appliance with a pipe clip, (clip not included).
Note: Condensate drain tube and pipe clip are available as a spare part from Rinnai, part number 90180944.
1
Drain Tube
Rubber Drain
Outlet
CAUTION
WARNING
2
90
120
RHFE-308FTR
75
120
RHFE-309FT
65
80
RHFE-556FTR~FDT
115
120
RHFE-557FTR
RHFE-561FT
80
RHFE-559FT
115
Dim ‘B’
*Dim ‘A
*Dim ‘A Dim ‘B’
RHFE-1004FTR-FDT 510mm 135mm
RHFE-1005FT-FDT 500mm 100mm
Heat Shields
(Drill lower heat
shield only)
Heat Shield
Heat Shield
Heat Shield
Heat Shield
Heat Shield
Back panel Back panel
Back panel
Back panel Back panel Back panel
CAUTION