Tech Bulletin

TB-151(01)
1 10/2019
Technical Bullen 151 - Ubbink Flexible Venng for M-Series Boilers
PURPOSE: To announce the approval of Ubbink Rolux® exible vent system components with the following Rinnai
M-Series Boiler models:
Combi Solo
M060C
M090C
M120C
M160C
M060S
M090S
M120S
M160S
INSTALLATION REQUIREMENTS:
Vent Opons Room Air (Non-Direct Vent) applicaons ONLY.
NOT approved for outside combuson air (Direct Vent).
Diameter 2 in. (60 mm)
Material Polypropylene (PP)
DO NOT combine vent components from dierent manufacturers.
Maximum Equivalent
Vent Length
M060S, M060C, M090S—60  (18.3m)
M090C, M120S, M120C, M160S, M160C—30  (9.1m)
Terminaon Vercal only. DO NOT run or terminate horizontally as condensate will not drain properly.
Bending Condions Bend radius: Must be larger than 7 in. (178 mm) (Figure 1)
Angle: Do not install in angle over 45° to vercal (Figure 2)
Clearances 0 (zero) clearance to combusble materials.
Installaon
Temperatures
Do not install while ambient temperatures are below 41°F (5°C). In colder weather, pre-warm
ex venng prior to installaon.
Addional
Requirements
Vent system connects to only one Rinnai M-Series Boiler.
Ubbink Rolux® venng components must be used throughout the enre vent system.
Do not combine with vent components from other manufacturers.
Do not store venng exposed to sunlight.
Venng must be enclosed and used with a rigid PP pipe to connect to the boiler (Figure 3
on next page).
Approvals/Codes Installaon must conform to the Rinnai Installaon and Operaon Manual that is shipped with
the unit, local codes, or in the absence of local codes, with the Naonal Fuel Gas Code, ANSI
Z223.1/NFPA 54.
Less than 45° angle
Figure 1 Figure 2
Larger than
7 in. (178 mm)
Radius