Technical Bulletin 152-Updated O2 Settings for M-Series Boilers
Rinnai America Corporaon • 103 Internaonal Drive, Peachtree City, GA 30269
Toll-Free: 1-800-621-9419 • Phone: 678-829-1700 • www.rinnai.us
©2018 Rinnai America Corporaon. Rinnai America Corporaon connually updates materials, and as such, content is subject to change without noce. Local, state,
provincial, federal and naonal fuel gas codes must be adhered to prior to and upon installaon.
The purpose of this technical bullen is to communicate the proper O2 sengs of the M-Series boilers.
Maximum Input Minimum Input
Boiler
Model
Natural Gas Liquid Propane Natural Gas Liquid Propane
M060C (Combi) 4.7% - 4.9%
5.0% - 5.2%
0.4% - 1.6%
Higher Than
Observed on
Maximum
Input
4.7% - 5.5%
M090C (Combi)
4.2% - 4.4% M120C (Combi)
M160C (Combi)
M060S (Solo)
4.7% - 4.9%
M090S (Solo)
M120S (Solo)
4.2% - 4.4%
M160S (Solo)
• The O2 percentage seng is required to be checked at commissioning, maintenance, faults, and adjusted if needed.
• Correct gas supply pressure must be conrmed before tesng O2. Refer to the O2 tesng procedures in the
“Commissioning” secon of the “M-Series Condensing Boiler Installaon and Operaon Manual.”
• Boiler front cover must be in place for accurate ue gas tesng.
NOTICE
The O2 percentage is required to be checked and adjusted aer a conversion from Natural Gas to
Liquid Propane, or from Liquid Propane to Natural Gas. Seng the O2 at maximum input must be
performed with a calibrated combuson analyzer that is set to the correct gas type.
IMPORTANT: The informaon in this Technical Bullen is intended to be performed by the Installer/Technician.
A trained and qualied professional must install, inspect, and leak test the boiler before use. The warranty will be voided
due to any improper installaon. The boiler must be commissioned by a licensed professional. The trained and qualied
professional should have skills such as: gas sizing; connecng gas lines, water lines, valves, and electricity; knowledge of
applicable naonal, state, and local codes; installing venng through a wall or roof; and training in installaon of
condensing boilers. Training for Rinnai boilers is accessible online at www.trainingevents.rinnai.us.
WARNING
EXAMPLE: Model M060CN (N=Natural Gas)
Maximum input from the factory is observed to be 4.7% O2. This is within the tolerance and will not need to be
adjusted. The unit on minimum input is 5.8% and is within the 0.4% - 1.6% higher range.
EXAMPLE: Model M120SP (P=Propane)
The boiler has been eld converted to Liquid Propane. The maximum input O2 is observed to be 5.4%.
This will need to be lowered. Aer adjusng maximum input O2 to 5.1%, minimum output is observed to
be 5.2%. This is within the tolerance for minimum input.