Installation Manual

76 Rinnai M-Series Condensing Boiler Solo Manual
North Facing Wall
Outdoor Temperature
Sensor
Outdoor reset is a built-in funcon to help maximize the eciency of the boiler. The design of this
funcon is to adjust the target temperature of the boiler relave to the outdoor ambient
temperature via the four outdoor reset curve opons included in the boiler parameters. The
outdoor ambient temperature is observed via the provided outdoor temperature sensor.
The outdoor temperature sensor should be mounted on a North facing wall of the house below an
eave to avoid direct sunlight (to prevent obtaining a false reading of the outdoor temperature). The
sensor should also be mounted away from any vent, duct, or other device that may create an
arcial heat source. The sensor should then be wired back to the outdoor temperature sensor
terminal on the boiler. Refer to the following secons for more informaon.