Use and Care Manual
Rinnai M-Series Condensing Boiler User’s Informaon Manual 13
Code Descripon Reason(s) Fault Locaon How to Resolve
1P1 Flow Check 1 Failed
Change in supply temperature of 12.6°
F to 27° F in one second
Central Heang
operaon
The boiler will aempt
to correct for 10
seconds
1P2 Flow Check 3 Failed
The supply water temperature is more
than 99°F higher than the return water
temperature
Central Heang
operaon
The boiler will aempt
to correct for 10
seconds
1P3 Flow Check 4 Failed
The return water temperature is 18° F
higher than the supply water
temperature
Central Heang
operaon
The boiler will aempt
to correct for 10
seconds
1P4 Filling Needed
Supply pressure is below the warning
pressure
Central Heang
operaon
Raise the supply
pressure above the
minimum pressure
201
Combi Domesc Hot
Water NTC Damaged
The Domesc Hot Water sensor has a
short or open circuit
Domesc Hot
Water operaon
Troubleshoot the
Domesc Hot Water
sensor
203
Tank NTC Sensor
Damaged
The tank probe has a short or open
circuit
Domesc Hot
Water operaon
Troubleshoot the tank
probe
303 PCB Fault PC board soware or hardware error PC Board Press the Reset buon
304 Too Many Reset
The Reset buon was pressed more
than 5 mes in 15 minutes
PC Board
Wait for 15 minutes to
elapse without pressing
the Reset buon
306 PCB Fault PC Board error PC Board Press the Reset buon
309 Gas Relay Check Failed
Flame detected for 3 seconds aer the
gas valve closed
PC Board Press the Reset buon
3P9
Scheduled Maintenance-
Call Service
The maintenance mer has expired PC Board
Reset the monthly
mer for the next
maintenance interval
reminder
501 No Flame Detected Flame not detected
Flame ignion/
detecon
Press the Reset buon
502
Flame Detected with Gas
Valve Closed (False
Flame)
Flame detected before the gas valve
opened
Flame ignion/
detecon
Troubleshoot the ame
rod, igniter, electrode,
and gas valve
504 Flame Li Loss of ame during burner operaon
Flame ignion/
detecon
Press the Reset buon
5P1 1stIgnit Failed
Flame not detected during the rst
ignion aempt
Flame ignion/
detecon
Fault will go away at the
end of the second
ignion aempt
5P2 2ndIgnit Failed
Flame not detected during the second
ignion aempt
Flame ignion/
detecon
Fault will go away at the
end of the third ignion
aempt
5P3 Flame Li Loss of ame during burner operaon
Flame ignion/
detecon
Fault will go away with
proper ignion
612 Fan Error Fan speed is too high or too low Fan/Vent Press the Reset buon
1P9
Water Pressure Dynamic
Check
No pressure change aer 5 seconds of
running the pump
Central Heang
operaon
The boiler will check the
pressure for 30 seconds
and the error will go
away with proper inlet
pressure
140
Water Pressure Dynamic
Check
Two 1P9 water pressure checks failed
Central Heang
operaon
Press the Reset buon