Polypropylene (PP) Common Venting Installation Instructions 25
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.
Check on whether local codes supersedes these clearances.
Avoid terminaon locaons near a dryer vent.
Avoid terminaon locaons near commercial
cooking exhaust.
You must install a vent terminaon at least 12”
above grade or snow line.
60"
V
V
(0.91 m)
between
terminals at
dierent levels
24"
V
(0.61 m) to wall or parapet
Additional Clearances
36"
24"
INS ID E
CO RNER
(0.61 m ) to an inside corner
(0.91 m) between
terminals at same
level
The vent for this appliance shall not terminate
Over public walkways; or
Near sot vents or crawl space vents or other
area where condensate or vapor could create a
nuisance or hazard or cause property damage; or
Where condensate or vapor could cause damage
or could be detrimental to the operaon of
regulators, relief valves, or other equipment.
Important consideraons for locang vent
terminaon under a sot (venlated or unvenlated
or eave vent; or to a deck or porch)
Do not install vent terminaon under a sot
vent such that exhaust can enter the sot vent
Install vent terminaon such that exhaust and
rising moisture will not collect under
eaves. Discoloraon to the exterior of the
building could occur if installed too close.
Do not install the vent terminaon too close
under the sot where it could present
recirculaon of exhaust gases back into the
combuson air intake part of the terminaon.
V
Represents the exhaust vent of the
common venng.
12”
X
Represents the combuson air vent of
the common venng.
X
V
V
V