Installation manual

Rinnai New Zealand Limited Neo Installation Manual: 11906-B
02-11
14
Masonry installaons
1. Check dimensions of the opening
Refer 'Enclosure dimensions' and if necessary bring them to the required dimensions.
Check the chimney height as inadequate height can eect product performance. Some
installations may require the chimney height to be extended to reduce down drafts.
2. Check ueway
Ensure there are no obstructions
Provide a rm, at and sealed base (sealed means no holes or openings in the replace)
Ensure adequate support of the appliance (if not properly supported noise and vibration
may result)
3. Install exiliner ue system
To ensure adequate draw for maximum performance of the appliance, Rinnai strongly
recommends the use of a Rinnai exiliner ue system for masonry installations. Failure to meet
this installation criteria may result in an unsafe situation. Performance issues resulting from
inadequate ueing is not covered by the warranty.
Installation without a exiliner is permissible in masonry installations as long as the chimney
has been checked for soundness and ability to achieve a good draw.
Chimney plate
Inbuilt masonry without a flexiliner flue
Inbuilt masonry with a flexiliner flue
Mortar
Approved chimney
cowl
Minimum
200 mm
Minimum
3.6 m
Chimney plate
Mortar
Approved chimney
cowl
Minimum
200 mm
Minimum
3.6 m
Adaptor
Flexible chimney
liner
Appliance
adaptor
Masonry installaon without a flexiliner flue Masonry installaon with a flexiliner flue