Installation & Servicing Instructions High efficiency condensing gas boiler Q85SN/Q130SN/Q175SN/Q205SN/Q175CN Q85SP/Q130SP/Q175SP/Q205SP/Q175CP CAUTION! Read this manual thoroughly before installing, servicing, putting into operation or using this boiler and vent system. WARNING! Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury (exposure of hazardous materials)* or loss of life. Refer to the user's information manual provided with this boiler.
Contents of instructions These installation instructions contain important information for the safe installation, start-up and maintanance of boilers with capacities 85,000 through 205,000 BTU/hr. These installation instructions are intended for professional installers, who have the necessary knowledge and are approved for working on heating and gas systems.
Content 2 3 4 5 6 Safety and general instructions.........................................................4 1.1 Designated use....................................................................4 1.2 Hazard definitions.................................................................4 1.3 Symbol definitions................................................................4 1.4 The following instructions must be followed.........................5 1.5 Follow these instructions for the space heating water.....
1 Safety and general instructions Please observe these instructions in the interest of your own safety. 1.1 Designated use The boiler is designed for heating water for a central heating system and, if applicable, generating domestic hot water. The boiler is delivered with a burner controller (MCBA) pre-installed.The boiler can be fitted with a modulating outdoor reset sensor ARV12 (included with the boiler) or an On/Off thermostat or relay panel end switch (accessories). 1.
1.4 The following instructions must be followed - The boiler must only be used for its designated purpose, as described in the Installation Instructions. Each unit is fitted with a data plate. Consult the details on this plate to verify whether the boiler is compliant with its intended location, e.g.: gas type, power source and venting classification. Only use the boiler with the accessories and spare parts listed.
1.5 Follow these instructions for the space heating water Unsuitable heating system water can cause the formation of scale or sludge, which affects system efficiency. It can also cause corrosion and reduce life of the heat exchanger. – You must follow Rinnai guidelines for boiler water quality. – Thoroughly flush the system prior to filling. – Follow the Rinnai cleaning instructions. – Never use water that has been treated by a reverse osmosis, D.I.
1.7 Relevant Installation, Service and User manuals – Approved vent system – Rinnai Boiler Applications Manual 1.8 Disposal – Dispose of the boiler packaging in an environmentally sound manner. – Dispose of components of the heating system (e.g. boiler or control device), that must be replaced in an environmentally responsible manner.
4) A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
4 Packaging and transportation 4.1 Scope of delivery The boiler is supplied ready for use. • Please check if the packaging is intact. • Check if all the items listed are included in the delivery.
5 Installation 5.1 Requirements for the installation room ! DANGER - Installation & Servicing Instructions Rinnai Q-Series - 10 The room where the boiler will be placed must always be frost free. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Never use or store any chlorinated detergents or halogenated hydrocarbons (e.g. in spraycans, solvents and detergents, paints, adhesives) in proximity of the boiler.
5.2 Fitting the boiler i NOTICE i NOTICE - Remove the packaging materials. - Do not tear the packaging. Take notice of the presence of the mounting template at the inside of the carton wrapper. Lay the boiler on its back during unpacking. When unpacking, the casing can be removed from the boiler. This part can be kept apart during installation. It must be placed on the boiler and fixed with the screw behind the door before the boiler is started up.
5.
Dimensions A B C D E F G H J K L N O P Q R S T U V1 V2 W X Y Z aa Height Width Depth Left side / vent Center to center / vent and air supply Back / vent Left side / gas pipe Left side / supply pipe Left side / return pipe Left side / condensate pipe Left side / expansion pipe Left side / cold water pipe Left side / hot water pipe Pipe length of g* Pipe length of c* Pipe length of f and r* Pipe length of e, k and w* Back / Center of pipe c* Back / Center of pipe g* Back / Center of pipe f, r, e, k and w* B
Dimensions Connection for combustion air supply and vent system g f1 r1 c g f1 r1 c g f1 r1 c e k w t f2 r2 boiler connections f2 r2 Boiler type Installation & Servicing Instructions Rinnai Q-Series Vent system / Combustion air supply g Gas pipe Supply pipe boiler side - f1 system side - f2 Return pipe boiler side - r1 system side - r2 Condensate pipe c 14 Expansion pipe e Cold water pipe k Hot wate
5.3.1 Plumbing Kits Rinnai boilers are supplied with a Plumbing kit from factory. Find below the dimensions. See chapter 6.1 for additional information. Plumbing Kit 2 Suitable for: Q85SN / Q85SP Q130SN / Q130SP 8.6” 219mm 4.7” 3.9” 119mm 100mm 2.0” 50mm 17.6” 448mm 5.2” 131mm 9” 229mm 14.2” 360mm 142 [5.6”] 16.4” 416mm Plumbing kit 2 Plumbing Kit 3 Suitable for: Q175SN / Q175SP Q175CN / Q175CP Q205SN / Q205SP 2.0” 50mm 4.7” 120mm figure 4 15” 381mm 10.2” 260mm 18.
5.3.2 Clearences from the boiler ceiling Min. 10" / 250mm 2" 50 24" 600 2" 50 wall 15.
5.4 Technical specifications Q-Series Q85SN Q85SP Q130SN Q130SP Q175SN Q175SP Q205SN Q205SP 175,000 51 157,000 45.9 172,400 50.2 167,500 48.8 85,000 25 77,000 22.5 84,000 24.7 82,000 24.1 130,000 38 117,000 34.2 127,600 37.3 117,000 36.5 175,000 51 157,000 45.9 172,400 50.2 167,500 48.8 205,000 60 184,000 54.0 202,200 59.1 184,000 57.4 % 98.5 98.8 98.2 98.5 98.5 % % W W V/Hz A 95.
6 Connecting the boiler The boiler has the following connection pipes; - The central heating circuit pipes. These must be connected to the Plumbing Kit by means of adapter fittings. See further chapter 6.1; - The expansion tank connection. Combi boilers only:It consists of a 3/4" (22 mm) steel pipe and can be connected to the expansion tank by means of 3/4" M-NPT adapter fitting. See further chapter 6.2; - The gas supply pipe.
P Low Loss Header T V1 V2 Service valve Service valve 1 11 7 2 6 5 8 9 3 10 4 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
6.1.1 Plumbing Kits and installation Rinnai supplies specific Plumbing Kits with each boiler type, which must be fitted directly underneath the boiler on the supply and return pipe. Find in chapter 5.3 the dimensions. Use of the Rinnai boiler without the plumbing kit will void the warranty. i NOTICE i NOTICE i NOTICE To protect the entire heating system we recommend installing a dirt particle trap in the return circuit.
- Boiler system flushing (Not Boiler heat exchanger) When replacing an existing boiler the heating system should be flushed with the old boiler in place before the new boiler is added to the system. If the old boiler has already been removed a bypass must be piped in when the new boiler is installed in order to facilitate the flushing of the system. The boiler must be valved off from the system, while the system is flushed.
13. If the installation is a zone system be sure to purge out each zone individually 14. Close the auto feed on the system (F1) 15. Close the return side purge station (BD2) and disconnect the hose (H3). 16. Open the main valve on the system return (V3) 17. Close the bypass valve below the plumbing kit (V4). 18. Open shutoff valves on both the supply and return connections on the plumbing kit (V1 and V2). 19. Clean out the dirt trap 20. Test the pH of the water that will be used for filling the system 21.
If the installation resistance is over the stated value; the pump will rotate at maximum capacity and the load will be adjusted until an acceptable temperature difference between supply and return water has been obtained. If, after this, the temperature difference is still not acceptable then the boiler will switch off and wait until an acceptable temperature has arisen. If an unacceptable temperature is detected, the control will repeatedly try to achieve water flow over the boiler.
6.1.2 Side mounting kit for the Low Loss header A side mounting kit for the low loss header is available as an accessory. This kit relocates the low loss header from directly below the boiler to the left side of the boiler only. The kit includes all the parts required to relocate the low loss header including all mounting brackets and material. This kit provides an alternative to for installations with height limitations and allows for an alternative piping installation.
6.2 Expansion tank An expansion tank must be part of the central heating system. The expansion tank must be appropriate to the water content of the installation. The pre-charge pressure depends on the installation height above the mounted expansion tank. The expansion tank is NOT a part of the delivery and should be sourced locally. Please refer to the expansion tank manufacturer for further information. The Combi boiler Q175C is equipped with an expansion tank connection.
6.4 Gas connection ! DANGER Only work on gas lines if you are licensed for such work. If these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death. ! WARNING Rinnai wall mounted boilers are built to run on Natural Gas or Propane Gas. The gas type the boiler is suitable for is indicated on the packaging and on the boiler by a blue label with Natural Gas or a green label with Propane Gas and on the identification plate on the boiler.
6.4.2 i NOTICE Gas connection with propane gas The gas supply connection must comply with local regulations or, if such regulations do not exist, with the National Fuel Gas Code, ANSI Z 223.1. For Canada, the gas connection must comply with local regulations or, if such regulations do not exist, with the CAN/CSA B149.1, Natural Gas and Propane Installation Code. Pipe sizing for propane gas - Contact gas supplier to size pipes, tanks, and 100% lockup gas pressure regulator.
6.5 Hot water supply (Combi boiler Q175CN/Q175CP) Connection of the drinking water installation should be performed according to the national secondary drinking water regulations. ! flow regulator valve i Do NOT use toxic chemicals, such as those used for boiler treatment in potable water heating systems used for space heating. DANGER NOTICE figure 12 The sanitary water pipes can be connected to the installation by use of adapter fittings.
6.5.3 Installing a valve kit A means to isolate the domestic indirect tank water heater for cleaning must be provide at installation. Refer to figure 13 for proper piping layout. A Rinnai valve kit can be used on domestic water connections for all combi boilers to allow for cleaning of indirect tank water heater and installation the domestic hot water pressure relief valve.
- The relief valve should be added to the hot water outlet line according to the manufacturer instructions. DO NOT place any other type valve or shut off device between the relief valve and the water heater. Do not plug the relief valve and do not install any reducing fittings or other restrictions in the relief line. The relief line should allow for complete drainage of the valve and the line. If a relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system.
6.7 Vent system and air supply system Provisions for combustion and ventilation air must be made in accordance with section, Air for Combustion and Ventilation of the National Flue Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 of 7.4 of CAN/CGA B149.1, Installation Codes, or applicable provisions of the local building codes. - i NOTICE 6.7.1 Do not store chemicals near the boiler or in rooms where the air is being supplied to the boiler. See the list on page 10.
6.7.
6.7.
6.7.3 Installation of the vent system i NOTICE Consult local and state codes pertaining to special building code and fire department requirements. Adhere to national code requirements. i NOTICE Follow the listed maximum length of vent systems, which are boiler output dependent. The maximum permissible lengths are listed in table 9, chapter 6.7.7. Decide how to install the exhaust and air intake system. You can choose among: - Concentric system The concentric connection is provided standard initially.
6.7.3.1 Boiler conversion from concentric to parallel A A. 1. Push the 2 clips slightly outwards 1 B B. 2. Pull the concentric adaptor out of the boiler 3. Press the cover in the connection at the back from inside out 2 3 C 10 9 7 4 6 8 C. 4. Push the 3" adapter into the connection at the back of the boiler (= air intake) 5. Pull the rubber seal around the bottom of the exhaust connector 6. Push the exhaust connector in the boiler, in the boiler exhaust pipe until 'CLICK' 7.
6.7.4 Recommended vent/air intake terminal position Terminals should be positioned as to avoid products of combustion entering openings into buildings or other vents. Maintain 12” of clearance above the highest anticipated snow level or grade or, whichever is greater. Please refer to your local codes for the snow level in your area.
i i NOTICE See Boiler Applications manual for additional venting information. NOTICE The termination shall be at least 4 feet (1,220 mm) for the US and 6 feet (1,830 mm) for Canada distance from electric meters, gas meters, regulators and relief equipment. (for room air application only) Horizontal vent systems should always be installed sloping towards the boiler (min. 1/4”/ feet, 21 mm/m), in order to avoid condensate retaining in the vent system.
Fittings or Piping Equivalent 45 degree elbow 90 degree elbow plastic pipe per foot concentric vent kit 12" (300 mm) minimum 12" (300 mm) minimum 12" (300 mm) minimum ! table 8 12" (300 mm) minimum 12" (300 mm) minimum Terminal positions PVC 6.7.5 m 0.91 1.83 0.30 1.52 Equivalent friction loss of PVC/CPVC EXHAUST INTAKE feet 3 6 1 5 figure 20 Direct vent closet and alcove installation For closet and alcove installation, CPVC material, instead of PVC, must be used in a closet/alcove structure.
6.7.6 ! DANGER Dimensioning of the exhaust and air intake duct The wall mounted boiler must be vented and supplied with combustion and ventilation air as described in this section. Ensure the vent and air piping and the combustion air supply comply with these instructions regarding vent system, air system, and combustion air quality. Inspect finished vent and air piping thoroughly to ensure all are airtight and comply with the instructions provided and with all requirements of applicable codes.
6.7.7 Combustion air and vent piping lengths. In the table below you find the maximum equivalent pipe length of the vent/air system based on 3" diameter. These lengths are for single pipe (room air), twin pipe, and concentric venting systems.
6.7.8 Calculation of compensation factor The compensation factor eliminates or reduces the natural effect of derate of maximum input caused by the resistance of the vent system and/or the impact of the altitude. 1. Determine the Compensation Factor Vent System CF(V) in the table below. Eq. length (ft) min 0 11 21 31 41 61 81 max 10 20 30 40 60 80 100 Q85 0 0 0 1 2 3 4 Boiler type Q130 Q175 CF (V) 0 0 0 2 2 4 4 6 6 10 8 15 10 n.a. Compensation factor vent system CP(V) Q205 0 3 6 10 n.a. n.a. n.a.
6.7.9 Room Air System (indoor combustion air) When using indoor air, Rinnai strongly recommends the use of an indoor air filter, P/N 808000025. This boiler requires adequate combustion air for ventilation and dilution of flue gases. Failure to provide adequate combustion air can result in unit failure, fire, explosion, serious bodily injury or death. Use the following methods to ensure adequate combustion air is available for correct and safe operation of this water heater.
Confined Space: (Small Room, Closet, Alcove, Utility Room, Etc.) A confined space is defined in the NFPA #54 as "a space whose volume is less than 50 cubic feet per 1000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating of all appliances installed in that space." A confined space must have two combustion air openings.
Using Indoor Air For Combustion When using air from other room(s) in the building, the total volume of the room(s) must be of adequate volume (Greater than 50 cubic feet per 1000 Btu/hr). Each Combustion air opening must have at least one square inch of free area for each 1000 Btuh, but not less than 100 square inches each. Using Outdoor Air For Combustion Outdoor air can be provided to a confined space through two permanent openings, one commencing within 12 in.
7 ! External domestic hot water tanks WARNING Note the local codes for requirements for connecting an external hot water cylinder to the boiler. The installation must comply to these codes. Depending on the domestic hot water requirements and comfort preferences various external hot water tanks can be connected to the boiler. Connecting an external hot water tank to the Q175C is NOT possible. Connecting an external hot water tank to the Q-Series solo boilers can be done in 2 ways: 1.
Connecting incoming power Lead the cable through the back part of the boiler using a strain relief and lead the cable through the cable supports to the Control Tower. Use a step drill bit to create a knockout in the black steel on the bottom of the boiler for a strain relief. A number of predrilled wholes can be enlarged to fit different strain relief and conduit connections.
X7 ! Installation & Servicing Instructions Rinnai Q-Series High Limit Switch T 220°F 120V 120V figure 28 CAUTION Label all wires prior to diconnection when servicing or replacing controls. Wiring errors can cause improper and dangerous operation electrical diagram 2 Amp. max.
Installation & Servicing Instructions Rinnai Q-Series electrical ladder diagram 48 figure 28a
9 Boiler controls The boiler is provided with a fully automatic microprocessor control, called CMS Control Management System. This control simplifies operation by undertaking all major control functions. Initially when power to the unit is switched on it will remain on standby. There is no indication LED on, until one of the program buttons is pressed. The control panel display will show the relevant state. When the installation is empty the display will show FILL.
9.1 Explanation of the function buttons 1 2 3 7 4 5 6 8 Boiler control panel i NOTICE figure 29 Only qualified personnel who are trained for servicing these boilers are permitted to make alterations in the controller to calibrate the boiler to the installation. 1. Display. See previous page for further information. 2. ON-OFF Switch This switch turns the power supply to the boiler on or off.
10 Starting up: Filling and de-aerating the boiler and installation ! CAUTION i NOTICE i NOTICE ! WARNING CAUTION Observe the following rules of safety: - All work on the unit must take place in a dry environment. - Rinnai units may never be in operation without their housing, except in connection with maintenance or adjustments (see Chapter 13 and 14). - Never allow electrical or electronic components to come into contact with water.
Freeze protection Freeze protection for new or existing systems must use glycol that is specially formulated for this purpose. This includes inhibitors, which prevent the glycol from attacking the metallic components. This should be for multi-metallic components. Make certain to check that the system fluid is correct for the glycol concentration and inhibitor level. The system should be tested at least once a year and as recommended by the producer of the glycol solution.
13 If A XX appears on the display, wait for 17 minutes; 14 Check the water pressure and if necessary top it up to 16 to 18 PSI 15 Close the filling loop; 16 Press the ‘STEP’-button; 17 Be sure that the filling loop is closed. 18 After the automatic de-aeration program (A XX) is finished the boiler will return to the Good state or Technical read out. Check the water pressure regularly and top off the installation when necessary.
FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do NOT try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
11 Adjustments When the boiler is installed the software has already been pre-programmed at the factory. All software adjustments of the boiler control are already pre-programmed for a heating system with radiators/convectors with a supply temperature of 176°F. The adjustments are described in the Parameter chapter on the following page.
Parameter Mode PARA . 1 2* FACTORY . 176°F 00 DESCRIPTION . maximum supply temperature CH type of CH installation: No pre-selection made. Radiators, air heating, or convectors: T max. supply 176°F K factor heating curve 2.3; gradient 10°F/min; gear differential 10°F RANGE . 68 - 176°F 00 - 04 00 01 DO NOT USE 3 4* max. 00 radiators with large surface areas or underfloor heating as additional heating: T max. supply 158°F K factor heating curve 1.
Service Mode . Error Mode ERRO VALUE Err.L - Err.5 1 2 3 °F 4 °F 5 kW 6 % DESCRIPTION boiler in operation with burner function on fan adjustable and burner off pump adjustable with burner on showroom position ON = active and OFF = non active RANGE OFF - max. OFF - max. OFF - max. ON - OFF . . DESCRIPTION Last saved error until 5 last previous errors error code operation status boiler supply water temperature T1 return water temperature T2 load (.. x3415 = ..
11.2 Activating factory settings (green button function) To activate the factory settings again please follow the next procedure (Note: all altered adjustments will be set back to the original factory settings that are accessible in the current service level the boiler is in either user or 123): - Select, when necessary, the technical read out; - Select with the MODE-button chapter PARA; - Press the STORE-button. The word "Copy" will appear and factory settings are active again.
13 i Commissioning Work on the boiler must be carried out by a competent person, using correctly calibrated instruments with current test certification. These installation instructions are intended for professional installers, who have the necessary knowledge and are approved for working on heating and gas systems. NOTICE Before the boiler is fired, ensure that the boiler and the system are well de-aerated and free of air. Purge the gas line between the gas meter and the boiler.
13.1 Testing for gas leaks Prior to start-up of the boiler you must check the external tightness of the gas supply valve and confirm this in the start-up report. ! WARNING - ! DANGER Before leaking testing the boiler, ensure all parts of the boiler such as electronics and wiring are properly covered and protected from the leak testing agent. Do not spray the leak testing agent onto cables, plugs, electrical connection lines or electronic circuit boards. Do not allow it to drip onto them either.
13.3 Checking the O2 i NOTICE ! WARNING The O2 percentage setting has to be checked at commissioning, maintenance and faults and adjusted if needed. The O2 percentage always must be checked and adjusted after a conversion from NG to LP or from LP to NG. This process must be done with a calibrated combustion analyzer that has been set to the correct gas type. This can be checked by means of the following procedure: - Remove the black cover of the gas valve by unscrewing the sealed screw.
Ending the O2 measuring procedure: - Press the - button until is shown (keep button pressed). With this the procedure has ended. - Replace the black cover on the gas valve and secure it with the screw. 13.4 Measuring the ionization current Installation & Servicing Instructions Rinnai Q-Series Ionization test 62 - Switch off the system using the Central Heating button and the DHW button - Disconnect the plug and the socket connection on the probe and connect the measuring device in series.
13.5 Installing the casing 1 CLOSE Installing air box 3 Installing casing 14 i Install the airbox and close all snap locks. See figure 34; - Install the metal casing on the boiler; - lock the casing by using the screw behind the door. See figure 35. figure 34 2 1 - 2 figure 35 Maintenance Maintenance or changes to the boiler may only be carried out by a qualified technician. NOTICE 14.
The air box OPEN Opening air box - Remove the transparant air box (figure 37); - Clean the box with a cloth with a simple (non-abrasive) cleaning agent; figure 37 14.2.1 Visual inspection for general signs of corrosion - 14.2.2 Check all gas and water pipes for signs of corrosion. Replace any pipes that are corroded. Measuring the ionization current See subsection 13.5 “Measuring the ionization current”. 14.2.3 Measuring the inlet gas pressure See subsection 6.4.1 and .
14.3 Maintenance activities i NOTICE 2 9 1 4 The fan unit and burner cassette (figure 38 to 40) (every 4 year maintenance) - Remove the electrical connection plug from the gas valve (1) and fan motor (2); - Loosen the nut (3) of the gas pipe under the gas valve; - Replace the gasket with a new one; - Loosen the front cross head screw (4) of the black plastic silencer; - After this turn the two clamping rods (9 and 10) ¼ turn and remove them by pulling them forward.
9 10 8 7 Siphon figure 41 13 14 11 Condensate tray ! 12 figure 42 Condensate trap and condensate tray (figure 41-43) (2 and 4 year maintenance) Step 1: Condensate trap - First remove the condensation cup (7); Check this for impurities. If there is not a lot of impurities it is not necessary to clean the condensate tray (Go to Step 3).
Visual inspection of the flame (2 and 4 year maintenance) The burner must flame evenly over the entire surface when operating correctly. The flame must burn with a clear, blue, stable flame. Check the flame through the inspection glass in the ignition probe (fig. 44). The flame pattern should be as shown in the figures below.
15 Parts of the boiler 4 2 1 3 7 5 16 15 6 8 17 T1 P1 19 T2 F Installation & Servicing Instructions Rinnai Q-Series G 68 T3 18 ATAG Q 1 2 3 4 5 6 7 8 R C 9 E W K 10 11 12 13 14 figure 45 heat exchanger ignition unit fan unit air inlet damper gas valve automatic de-aerator ceramic burner cassette DHW tank (Q175C) 9 10 11 12 13 14 operating panel Control Tower (CMS) water filter return CH three-way valve (Q175C) circulation pump thermostatic mixing valve (Q175C) 15
16 Blocks and Errors 16.1 Error indication (short reference) A detected error is indicated on the display by means of blocking or error messages. A distinction should be made between these two messages due to the fact that blocking can be of a temporary nature, however, error messages are fixed lockings. The control will try its utmost to prevent locking and will temporarily switch off the unit by blocking it. Hereunder is a list of some messages. Blocks with a number in the last 2 positions.
i NOTICE The following pages describes more detailed follow up instructions for solving blockings, errors and practical circumstances. These instructions are only for by Rinnai trained installers and technicians. 16.2 Blocks An error, which has been detected, is indicated on the display by a block message. Blocks can be temporary in nature. The controller will do everything possible to prevent a system lock and temporarily switching off the boiler as a result of a block.
16.3 Errors Description Solution Incorrect flame formation. boiler has not been burning but an ionization flow (flame) has still been detected Check whether the ionization cable and/or the electrode are responsible for a possible short-circuit. Remove the plugs from the ionization cable connected to the control unit and to the electrode. Now using a universal meter take a measurement between the ionization connection and the ground, now refit it part by part until a short-circuit takes place.
Code Description Solution Control unit error 1 Anticipation resistance wire not When a power stealing room stat device is placed the connection terminal present needs to be provided with the special anticipation resistance wire. 2 Software error control unit. Replace the control unit. The controller will automatically load the program into the new control unit. Control unit error Incorrect data will be detected in case of a poor connection between the control unit and the display.
Description Solution No signal from the fan The fan is not running. Check the wiring to the fan and the control unit and/ or the 24 volt power supply to the fan Wiring and voltage are OK and error is repeated. Replace the fan Negative pressure on vent system (pressure difference) Check vent system. Vent system and air intake system must be installed according installation instructions. IF vent system is OK: Replace fan internal shut down of supply sensor T1 Check the data in Error mode.
Code Description Solution contact for return sensor T2 open Check the data in Error mode. Boiler data during error: 1 Error = 37 2 Operational status = 00 3 Flow temp. = xx* 4 Return temp. = -22 5 kW burner = 00** 6 % pomp = xx* * = variable values **= x3415=BTU/hr Check the wiring. check the wiring for the sensor The wiring is OK but the error is repeated. Remove the plug from the flow sensor as a result of which Error 32 occurs Replace the sensor. Control unit error Software error control unit.
16.4 Other Errors Description Central heating but no domestic hot water 1. Hot water but no central heating Central heating installation gets hot without being requested Insufficient quantity of hot water Temperature drop of the DHW (Combi) -Key of the DHW program is not switched on Solution Switch on DHW program on the Control Tower 2. Cylinder sensor or thermostat defective. Replace cylinder sensor or thermostat 3.
Complaint Description Solution temperature drop of the Solo hot water with the DHW cylinders 1. Synchronising valve Check the setting in accordance with the illustrated DHW cylinder installation instructions 2. Thermostatic mixing valve incorrectly set Adjust by measuring the temperature 3. Hot water temperature too low Check PARA chapter Step No. 31 or RS100 is set too low. Check the functioning and wiring of the DHW sensor T3 4. Hot water power for the boiler is set too low.
Installation & Servicing Instructions Rinnai Q-Series
02 01 Parts casing Q-Series Installation & Servicing Instructions Rinnai Q-Series Pictured: E75CN, E110CN E75CP, E110CP m a n u a l WARNING! If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. - Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. - WHAT TO DO IF YOU SMELL GAS - Do NOT try to light any appliance. - Do NOT touch any electrical switch.
CASING 25/38 CASING 51/60 CASING 51C DOOR CASING Q CPL. USER MANUAL Q-SERIES INSTALLATION MANUAL Q-SERIES BOILER COVER BOLT M5X16 (SET OF 5 BOLTS) Q175C Q85S Q130S Q175S Q205S N P N P N P N P N P OSS3 OSS1 OSS2 OSS3 OSS4 809000011 X X X X 809000012 X X X X 809000013 X X 809000010 X X X X X X X X X X 800000010 X X X X X X X X X X 800000011 X X X X X X X X X X 809000126 X X X X X X X X X X Part No.
61 44 63 62 60 59 83 56 55 54 53 52 51 47 46 45 43 41 40 39 38 37 49 36 35 34 33 32 64 31 30 Parts heat exchanger Q-Series Installation & Servicing Instructions Rinnai Q-Series
CLAMP BAR TOP PART H.EX. LONG TOP PART HEAT EXCH. SET OSS1 TOP PART HEAT EXCH. SET OSS2 TOP PART HEAT EXCH. SET OSS3/4 BOLT M 5X16 (5 PER PACKAGE) GASKET FAN/TOP PART H.EX.
95 93 94 92 91 90 87 100 78 77 89 82 81 Parts rear wall Q-Series Installation & Servicing Instructions Rinnai Q-Series 84 96 97 98 114 115 99 103a 103 112 113 104a 104 111a 110 111 118 119 105 106 107 108a 108 109 116 101 102 117
COVER AIR SUPPLY Ø80mm CONCENTRIC FLUE ADAPTOR 80/125"MM GASKET AIR INTAKE ø80 SHR FLUE ADAPTER 80mm x 3" COVER AIR SUPPLY Ø125mm FLUE GAS SYSTEM PP SET OSS1 FLUE GAS SYSTEM PP SET OSS2 FLUE GAS SYSTEM PP SET OSS3/4 PLUG MEASURING POINT PARALLEL FLUE PIPE GASKET FLUE GAS PIPE PP GASKET AIR SUPPLY 5" AIR BOX BACK Q85S 7 Q130S AIR BOX BACK Q175S, Q175C & Q205S PLUG MEASURING POINT CONCENTRIC FLUE PIPE O-RING ø19.50X1.80 TRAP TRAY CONDENSATE DRAIN PIPE Q O-RING Ø12.42X1.
return sensor DHW sensor flue gas sensor 150 T2 158 T3 156 T5 151 P1 160 water pressure sensor 159 HLS high limit switch supply sensor 151 150 152 130 156 159 158 Parts electrical components Q-Series Installation & Servicing Instructions Rinnai Q-Series 152 T1 84 1 5 6 L N 4 230 V~ Pomp extern 3 L N 2 230 V~ Netaansl. 7 9 L 10 N 11 L 230 V~ 12 13 14 15 16 17 Boileraansluiting 3-Wegklep Sensor CV WW N 132 8 N 230 V~ Regelaar 8A.35.22.
805000010 805000011 805000045 805000012 805000014 805000013 805000015 805000016 805000017 805000018 805000021 805000022 805000023 805000024 805000026 805000027 805000028 805000029 805000013 805000048 805000031 805000023 Part No. Installation & Servicing Instructions Rinnai Q-Series 130 TRAFO 120V/24V SCREW 3,5X 9,5 VERZ.D7983 (5 PER PACKAGE) 131 CONTROL TOWER COMPLETE 132 HARNESS Q RAC STICKER CONNECTION TERMINAL HARNESS Q 120V + MAINS SWITCH CONNECTOR 2-POLE PURPLE CONNECTOR 2-POLE BLACK CONNECT.
205a 205 200 Parts tank (Combi boilers) Q-Series Installation & Servicing Instructions Rinnai Q-Series 204 206 207 208 209 202 211 212 210 213
MINI-TANK 6.6 GLN Q175C ADAPT.FITT+DOS.VLVE 4.75 GLN/MIN RED KNEE FITTING 15MM PIPE Ø15 COLD Q CONNECTION SET 15 X 3/4" NPT PIPE ø15 HOT-MIXING VALVE Q CROSS COMPR.FITTING 15MM Q PIPE Ø15 COLD MIXING VALVE Q THERM. MIX VALVE ø15 COMPR. Q PIPE Ø15 MIX Q FERRULE COMPR FITTING 15MM BRASS NUT 1/2" G BRASS COMPR. 15 STRAP CYLINDER/EXP.
307 306 305 304 301 300 Parts plumbing kit Q-Series Installation & Servicing Instructions Rinnai Q-Series 302 303 308
804000062 804000063 804000065 804000066 804000057 804000058 804000053 804000054 807000077 809000101 809000102 807000078 807000079 807000080 807000081 Part No. Installation & Servicing Instructions Rinnai Q-Series 300 PLUMBING KIT #2 FOR Q85S/Q130S PLUMBING KIT #3 FOR Q175S/Q175C/Q205S 301 COMPRESSION FITTING 28MM COMPRESSION FITTING 35MM 302 NUT COMPR FITTING 28MM NUT COMPR FITTING 35MM 303 FERRULE COMPR FITTING 28MM FERRULE COMPR FITTING 35MM 304 SAFETY VALVE PLUMBING KIT 305 INSOLATION PACK PL.
Installation & Servicing Instructions Rinnai Q-Series 18 90 Parts list vent system Vent Products Listed and Tested Vent Products for E75C, E110C, Q85S, Q130S, Q175S, Q175C and Q205S Manufacturer Descriptions Heatfab DGV 3"/5" Conc Air Intake Tee 3" DGV 3"/5" Conc X 12" Length Concentric DGV 3"/5" Conc X 31" Length DGV 3"/5" Conc Horz Term Adapter DGV 3"/5" Conc Vert Term Adapter Rain Cap 3"- Adapter to fit into 80 mm Flue Collar 3"- 12 Length 3"- 31" Length Twin Pipe 3"- 90 Deg Tr Elbow 3"- Screen Termi
Vent Manufacturer Contact Information for Installation Instructions and Parts Lists: Heat-Fab Telephone: 800-772-0739 Fax: 413-863-4803 cystsvc@heat-fab.com www.heatfab.com IPEX Telephone: 800-463-9572 905-403-0264 Fax: 905-403-9195 www.ipexamerica.com Rinnai/Ubbink Telephone: 800-621-9419 Fax: 678-829-1666 www.rinnai.us York International Telephone: 405-364-4040 877-874-7378 www.york.com/products/unitary/ Simpson Dura-Vent Telephone: 518-463-7284 Fax: 518-463-5271 sales@duravent.com www.
Installation & Servicing Instructions Rinnai Q-Series Appendix A - Outoor Reset Sensor Data 92 R 25 °C 12 kΩ R 100 ° C 950 Ω B25/85 3750 K Temperature coefficient -4,2 %/K NTC [kOhm] -30 171.70 -20 98.82 -10 58.82 0 36.10 10 22.79 20 14.77 25 12.00 30 9.81 40 6.65 50 4.61 60 3.25 70 2.34 80 1.71 90 1.27 100 0.95 110 0.73 120 0.
Appendix B - Resistance table NTC sensors -4 -0.4 3.2 6.8 10.4 14 17.6 21.2 24.8 28.4 32 35.6 39.2 42.8 46.4 50 53.6 57.2 60.8 64.4 68 71.6 75.2 78.8 82.4 86 89.6 93.2 96.8 100.
Distributor for the USA R i n n a i A m e r i c a C o r p o r a t e • 1 0 3 I n t e r n a t i o n a l D r i v e • P e a c h t r e e C i t y, G A 3 0 2 6 9 Toll Free: (800) 621-9419 • Tel: (678) 829-1700 • Fax: (678) 829-1666 • E-mail: info@rinnai.us • Internet: www.rinnai.us E. & O. E. This renewed publication cancels all previous installation instructions. The company reserves the right to change the specifications and dimensions without prior notice.