User manual
Installation & Servicing Instructions Rinnai Q-Series
25
6.2 Expansiontank
An expansion tank must be part of the central heating system. The expansion tank
must be appropriate to the water content of the installation. The pre-charge pressure
depends on the installation height above the mounted expansion tank. The expansion
tank is NOT a part of the delivery and should be sourced locally. Please refer to the
expansion tank manufacturer for further information. The Combi boiler Q175C is
equipped with an expansion tank connection. This pipe is connected with the three
way valve and boiler pump.
Fillexpansiontanktoaminimumof14.5psi.
Fortheboilertofunctioncorrectly,itisnecessarytoconnecttheexpansion
tanktotheexpansiontankconnectionontheboiler.Iftheexpansiontankisnot
connectedtothesuppliedconnectiondamagetotheboilermayoccur.
Note:
The solo boilers Q85S, Q130S, Q175S and Q205S can be provided with an optional
internal three way valve. When this valve is installed in the boiler, the boiler is provided
with an expansion tank connection. This pipe is connected with the three way valve
and boiler pump.
Fortheboilertofunctioncorrectly,itisnecessarytoconnecttheexpansion
tanktotheexpansiontankconnectionontheboiler.Iftheexpansiontankisnot
connectedtothesuppliedconnectiondamagetotheboilermayoccur.
See the Rinnai Boiler Applications Manual for further information regarding placement
of the expansion tank in the system. See the Rinnai 3-way valve indirect tank
installation manual for further information regarding the installation of the 3-way valve
indirect tank kit.
Theboilercannotbeusedwithanopentypeexpansiontank.
6.3 Underoorheatingsystem(plasticpipes)
When using oxygen-permeable pipes, e. g. for oor heating systems, you must
separate the system using plate heat exchangers.
Norecoursecanbemadetothetermsofthewarrantyintheeventoffailureto
observetheregulationspertainingtoplasticunderoorheatingpipes.
NOTICE
i
NOTICE
i
NOTICE
i
NOTICE
i
NOTICE
i