6.4 Gasconnection
Onlyworkongaslinesifyouarelicensedforsuchwork.
Ifthese instructions are not followedexactly, a re orexplosion may result
causingpropertydamage,personalinjuryordeath.
RinnaiwallmountedboilersarebuilttorunonNaturalGasorPropaneGas.
Thegastypetheboilerissuitableforisindicatedonthepackagingandonthe
boilerbyabluelabelwithNaturalGasoragreenlabelwithPropaneGasand
ontheidenticationplateontheboiler.
Firstchecktheidenticationplateontheboilerforthesuitablegastype.
Donotusetheboilerforanothertypeofgasthanindicatedontheidentication
plateoftheboiler.Thiswillcauseimproperfunctioningandcandamagethe
boiler.
Natural gas: refer to chapter 6.4.1
Propane gas: refer to chapter 6.4.2
6.4.1. Gasconnectionwithnaturalgas
The gas supply connection must comply with local regulations or, if such
regulationsdonotexist,withtheNationalFuelGasCode,ANSIZ223.1.
ForCanada,thegasconnectionmustcomplywithlocalregulationsor,ifsuch
regulationsdonotexist,withtheCAN/CSAB149.1,NaturalGasandPropane
InstallationCode.
Pipesizingfornaturalgas
Contact gas supplier to size the gas supply line and meter.
Gaspiping
A sediment trap must be installed upstream of the gas controls.
The boiler gas pipe is equipped with external 3/4" M-NPT thread, onto which the tail
piece of the gas shut off valve can be connected. Use appropriate sealing.
The connection to the boiler must include a suitable method of disconnection and a
gas control valve must be installed adjacent to the boiler for isolation purposes. The
nominal inlet working gas pressure measured at the boiler should be 7" W.C. (18 mbar)
for Natural gas (Gas A). Maximum pressure with no ow (lockup) or with the boiler
running is 10.5 inches W.C. Minimum pressure with the gas owing (verify during
boiler startup) is 4.0 inches W.C.
The gas pipe must be tted to the gas valve free from any strain.
Makesurethatthegaspipesystemdoesnotcontaindirt,particularlywithnew
pipes.
Alwayscheckthesafetyofthegaspipesystembymeansofabubbletestusing
leak-searchspray.
The boiler and its individual shut off valve must be disconnected from the
gassupplypipingsystemduringanypressuretestingofthatsystemattest
pressuresinexcessof1/2PSI(3.5kPa).
Theboilermustbeisolatedfromthegassupplypipingsystembyclosingits
individualmanualshutoffvalveduringanypressuretestingofthegassupply
pipingsystemattestpressuresequaltoorlessthan1/2PSI(3.5kPa).