User manual
Installation & Servicing Instructions Rinnai Q-Series
34
6.7.3 Installationoftheventsystem
Consult local and state codes pertaining to special building code and re
departmentrequirements.Adheretonationalcoderequirements.
Follow the listed maximum length of vent systems, which are boiler output
dependent.Themaximumpermissiblelengthsarelistedintable9,chapter6.7.7.
Decide how to install the exhaust and air intake system. You can choose among:
- Concentricsystem
The concentric connection is provided standard initially.
The boiler concentric connection diameter is 3"/5" (80/125 mm), to which the venting
and air supply system can be tted, with or without elbow pieces. The maximum
permissible pipe length is displayed in table 9, chapter 6.7.7.
- Parallelsystem
The boiler can be converted to a parallel system with supplied adapters.
It is possible to use a parallel pipe connection of 2x 3". In this case a separate supplied
kit, with 2 vent adapters 3" (ø80mm), cover 5" (ø125mm), vent exhaust pipe and
gaskets should be tted instead of the concentric vent adapter on top of the boiler.
See chapter 6.7.3.1 for installation. The maximum permissible pipe length is set out
in table 9, chapter 6.7.7.
-RoomAirSystem(indoorcombustionair)
The boiler can use room air for combustion. If this option is selected the boiler must
rst be converted to the parallel system. A single exhaust pipe can then be tted.
It is required to use a room air lter (Part nr. 808000025) when using indoor air for
combustion. See chapter 6.7.3.2 for installation. The maximum permissible pipe
length is set out in table 9, chapter 6.7.7.
RinnaistronglyrecommendstheuseoftheroomairlterincaseofRoomAir
System(indoorcombustionair).
Whentheboiler is installedinanyoftheareaslisted in chapter 5.1,"Areas
likelytohavecontaminants"oranyareaexposedtothecontaminantslistedin
chapter5.1,thensealedcombustionisrequired.
Weadvisetoinstallaventsystemoutoftheventingsystemprogramsuppliedby
Rinnai(Seechapter19PartslistVentsystem).Forfurtherinformationaboutthe
availablecomponentsoftheventingandairsupplysystemwerecommendyou
consultRinnaiandtheInstallationinstructionsandpartslistdocumentation.