Installation & Servicing Instructions Rinnai Q-Series
41
!
WARNING
Compensation factor vent system CP(V) table 10
Compensation factor altitude CP(A) table 11
Q85 Q130 Q175 Q205
min max
0 10 0 0 0 0
11 20 0 0 2 3
21 30 0 2 4 6
31 40 1 4 6 10
41 60 2 6 10 n.a.
61 80 3 8 15 n.a.
81 100 4 10 n.a. n.a.
CF(V)
BoilertypeEq.length(ft)
min max
0 1
1,000 2,000
2,000 3,000
3,000 4,000
4,000 5,000
5,000 6,000
6,000 7,000
7,000 8,000
8,000 9,000
9,000 10,000
Altitude(ft) Boilertype
Q85
,
Q130
,
Q175
,
Q205
CF(A)
0
6
12
18
24
54
30
36
42
48
NOTICE
i
6.7.8Calculationofcompensationfactor
The compensation factor eliminates or reduces the natural effect of derate of maximum
input caused by the resistance of the vent system and/or the impact of the altitude.
1. Determine the Compensation Factor Vent System CF(V) in the table below.
2. Determine the Compensation Factor Altitude CF(A) in the table below.
Any application or installation above 10,000 must be reviewed by Rinnai's
Engineeringgroup.Thisistoensuretheproductisinstalledandtheoverall
system is designed properly and that the units are commisioned properly.
NotinvolvingofRinnai'sEngineeringgroupwouldresultinnosupportofthe
productandnowarranty.
3. Calculate the Compensation Factor Total CF(T):
CF(T) = CF(V) + CF(A)
The result is the setting for Parameter 73.
Change parameter 73 according to this result. See Chapter 11.1 how to change
parameters.
Example of calculation:
Q175
Eq. lenth vent system (taken from previous example) 46 ft CF(V) = 10
Altitude 7,200ft CF(A) = 42 +
CF(T) = 52
Parameter setting (Par. 73) = 52
Donotovercompensatetheboilerbysettingahighervaluethancalculated,
otherwisetheboilercouldbeseriouslydamaged.