10 Startingup:Fillingandde-aeratingtheboilerandinstallation
CAUTION
Observe the following rules of safety:
- All work on the unit must take place in a dry environment.
- Rinnai units may never be in operation without their housing, except in connection
with maintenance or adjustments (see Chapter 13 and 14).
- Never allow electrical or electronic components to come into contact with water.
NOTICE
Carry out the following tasks in connection with maintenance, etc. to an already-
installed unit:
- Shut down all programs
- Close the gas shut off valve
- Shut off the power at the main power switch
- Close the service valves (supply and return)
NOTICE
Take note of the following when maintenance or adjustments are needed:
- The unit must be able to function during these activities; for this reason, the unit’s
supply voltage, gas pressure and water pressure must be maintained. Ensure that
this is not a source of potential danger during these activities.
Followingmaintenanceorotheractivities;alwayschecktheinstallationofall
partsthroughwhichgasows(withbubbletestusingleak-searchspray).
10.1Requirementsofthewatersystem
Before lling the heating system, the complete system, including all zones, must be
thoroughly cleaned and ushed to remove sediment. Flush until clean water runs
free of sediment. Rinnai suggests using an approved system cleaner to ush the
system, but not the boiler. Always use Rinnai approved antifreezes. See the list at
the end of this chapter. Never use reverse osmosis, D.I., or distilled water for lling
the heating system.
Do not use petroleum-based cleaning or sealing compounds in the boiler
system. Damage of seals and gaskets in boiler and system could occur,
resultinginsubstantialpropertydamage.
The central heating installation needs to be lled with potable water.
Useonlypotablewaterorapprovedglycolforllingtheheatingsystem.
Whenthewaterhardnessofthellingwaterexceeds>10.5gpg(200mg/L)and
thevolumeoftheinstallation>20L/kW(5.2gallons/3,412BTU)thewaterhasto
betreateduntilbelowthemaximumvalueof10.5gpg(200mg/L).
ThepHvalueoftheinstallationwatermustbebetween6.5and8.5.
Check the pH value using proper equipment or by having the water analyzed by a
water treatment company.
If pH differs from above, contact Rinnai engineering for further assistance.
Failuretoadheretothewaterqualityrequirementswillvoidthewarranty.
!