11 Adjustments
When the boiler is installed the software has already been pre-programmed at the
factory. All software adjustments of the boiler control are already pre-programmed for
a heating system with radiators/convectors with a supply temperature of 176°F. The
adjustments are described in the Parameter chapter on the following page.
In certain cases parameters have to be altered in case of :
- Lower supply temperature
- High altitude/long vent length
The venting / altitude calculation must always be performed during
commissioningoftheboiler.
Read through the Parameter chapter to adjust the boiler to its installation.
Contact Rinnai in case of doubt.
Onlyqualiedpersonnelwhoaretrainedforservicingtheseboilersarepermitted
tomakealterationsinthecontrollertocalibratetheboilertotheinstallation.
11.1Alteringadjustments
PresstheMode-buttonfor5seconds.
The display shows COdE followed by an arbitrary number;
Pressbymeansofthe+orthe-buttonuntilthecodeC123isshown;
PresstheSTORE-buttontoconrmthecode(codeblinks1x).
Now you have acces to the installer level. There are 4 chapters:
• Parameters
• Information chapter (no adjustments possible)
• Service chapter
• Error-chapter (no adjustments possible)
The content of the chapters is described on the following pages.
PressbrieytheMODE-buttontoselectoneofthe4chapters,i.e.PARA;
PressbrieyandreleasetheSTEP-buttontoselectaParameter
(parameter visible on the left, value on the right) ;
Alterthevalue,ifnecessary/possible,bymeansofthe+orthe-button
PressbrieyontheSTORE-buttontoconrmthealteration.
When you have to change more values, repeat from step 5.
PressonceormoreontheMODE-buttonuntilStBYorGoodisshown:
After a few seconds the text StBY will be replaced by the technical read-out
or Good-state (Depending from the position the acces code is entered)
When you want to return from an arbitrary position to the original read out
press once or more on the MODE-button until StBY is shown.
If no single button is used within 20 minutes the display will return automatically to its
original read-out (Good state or technical read out)
!
CAUTION