Installation & Servicing Instructions Rinnai Q-Series
6
1.5 Followtheseinstructionsforthespaceheatingwater
Unsuitable heating system water can cause the formation of scale or sludge, which
affects system efciency. It can also cause corrosion and reduce life of the heat
exchanger.
– You must follow Rinnai guidelines for boiler water quality.
– Thoroughly ush the system prior to lling.
– Follow the Rinnai cleaning instructions.
– Never use water that has been treated by a reverse osmosis, D.I., or distilled water
to soften the water to ll the heating system.
– Do not use inhibitors or other additives unless approved by Rinnai for that purpose!
– When frost protection of the heating system is desired, only use Rinnai-approved
antifreezes. The allowed maximum concentration is 50%.
– When using oxygen-permeable pipes, e. g. for under oor heating systems, you
must separate the system from the boiler using plate heat exchangers.
–
Valve off boiler while ushing system, do not introduce any system cleaner into the
boiler loop. Flush system thoroughly to remove all system cleaner before lling boiler.
Approvedantifreeze: • Rhomar RhoGard Mutli-Metal (AL safe)
(max. concentration 50%) • Noble Noburst AL
Approvedsystemcleaner: • Noble Noburst Hydronic System Cleaner
• Fernox F3 Cleaner
• Rhomar Hydro-Solv 9100
ThesystemcleanersfromNoBurst,Rhomar,andFernoxarenottobeusedin
theboiler.Theboilermustbeclosedoff(valvedoff)fromtherestofthesystem
ornotconnectedwhilethecleanersareinthesystem.Thesystemshouldthen
be drained and then thoroughly ushed with clean water to remove all the
systemcleaner.
Approvedinhibitors: • Rhomar Pro-tek 922
• Noble Noburst AL inhibitor
See the Rinnai Boiler Applications Manual or Chapter 6 and 10 of this manual for
additional information.
Ifproblemsoccurwhenusingsanitarywaterwithachlorinecontent
higherthan150mg/l,norecoursecanbemadetothetermsofthewarranty.
1.6 Tools,materialsandadditionalequipment
For the installation and maintenance of the boiler you will need:
– Standard tools for space heating, gas and water tting
– Digital manometer that is capable of reading both positive and negative pressures
– Combustion analyzer (intended for use with condensing boilers)
– Digital multimeter
– pH digital meter
– Metric Allen wrenches
– Metric socket wrenches
In addition, a handtruck with a fastening belt is useful.
For maintenance of the boiler you will need, apart from standard tools for space
heating, gas and water ttings the following items:
- Rinnai toolkit Q and E-Series