Install Instructions

Installation & Servicing Instructions Rinnai Q-Series
68
Visual inspection of the ame (2 and 4 year maintenance)
The burner must ame evenly over the entire surface when operating correctly. The
ame must burn with a clear, blue, stable ame.
Check the ame through the inspection glass in the ignition probe ( g. 44).
The ame pattern should be as shown in the gures below.
Further checks:
- Inspect the pressure relief valve
- Clean the water lter in the return pipe
- Check the pH of the water or glycol/water mixture.
The combustion must be checked and adjusted if required at both the 2
year/4000 hour and 4 year/8000 hour service intervals with a properly working
combustion analyzer.
Verify proper operation after servicing. Always reset the service interval counter after
full maintenance interval (every 4 years or 8000 hours of operation).
14.3.1 Reset service interval counter
At 8000 hours of use, “SERVICE” will scroll across the display. “Good” will display
as well alternatively.
To reset the 8000 hour service noti cation:
- Enter the 1st Tier Settings: 123 Code
- Brie y press “Mode” again until the Service Chapter is displayed (SERV)
- Hold the “Store” button until SERV ashes once—the service noti cation will no
longer show during normal operation and the countdown to service will reset to
8000.
14.4 Limited warranty
For warranty conditions refer to the warranty supplied with the boiler.
Inspection glass figure 44
SATISFACTORY
Ignition probe
blue ame
UNSATISFACTORY
Ignition probe
yellow ame
NOTICE
i
Water filter figure 44a