Installation manual

Rinnai 12 RF1800 OIM
VENTILATION
IMPORTANT
This appliance is a decorative ame effect appliance, the space or room in which the unit is
installed must have adequate xed ventilation compliant with the requirements of AS/NZS 5601.
For Decorative Gas Log Fires this requires that one or more openings with a combined free
ventilation area of not less than 314 cm² shall be provided for each appliance.
The opening may be provided by any of the following options, provided that there is a ventilation
path to outside that is unobstructed by building material or insulation:
a) Directly through an outside wall (preferred option).
b) Through to an outside wall but offset.
c) Into a cavity ventilated to outside.
d) Into an underoor space ventilated to outside.
e) Into a roof space ventilated to outside.
FLUE REQUIREMENTS
IMPORTANT
ONLY the Rinnai ue components described in this manual are to be used with this appliance.
The installation of the ue system MUST comply with the requirements of AS/NZS 5601.
Examples of the available ue component congurations are shown below.
B1
B2
B3/4
B2
C
C
Y Piece - Direct
B3/4
Twin - Direct
FRONT VIEWFRONT VIEW
A
A
A
A
474mm
E
A
A
A
A
Twin - Extended OffsetTwin - Offset
A
A
SIDE
VIEW
SIDE
VIEW
GG
A
EE
E
SIDE
VIEW
SIDE
VIEW
B
Y Piece - Offset
A
E
E
Y Piece - Extended Offset
C
C
E
A
E
C
C
B
B
B
F
C
F
A
G
DDD
B
F
C
F
A
(Option 1)(Option 1)
(Option 2)
(Option 2)
2.4m*
3.6m*
2.4m*
3.6m*
3.6m*
3.6m*
* This is the minimum flue height for the configurations as shown, for additional bends increase the flue height in accordance with AS/NZS 5601.
Y Piece - Direct: Allows the twin ues to be joined to a single ue for termination. It is recommended
that the ue be taken vertically as high as is practicable before joining to the Y Box assembly.
Y Piece - Offset / Extended Offset: Same as “Y Piece - Direct” with the inclusion of one 45° offset
or extended offset.
Twin - Direct: Uses two separate ue pipes to the ue termination point.
Twin - Offset / Extended Offset: Same as “Twin - Direct” with the inclusion of one 45° offset or
extended offset.
Minimum
Flue Heights
Y Piece Direct Y Piece Offset Twin - Direct Twin - Offset Twin - Extended Offset
2.4m 3.6m* 2.4m 3.6m* 3.6m*
* Only 1 x 45° bend set can be used on each ue for Offset or Extended Offset ue installations.
Additional bends may be utilised, however this will then require that additional vertical lengths
also be included to increase the ue height in accordance with AS/NZS 5601.