User Guide
14 RH180 Manual
Combuson air provided to the appliance
should not be taken from any area of the
structure that may produce a negave pres-
sure (i.e. exhaust fans, powered venlaon
fans).
Conned Space:
(Small Room, Closet, Alcove, Ulity Room, Etc.)
A conned space is dened in the Naonal Fuel Gas
Code, ANSI Z223.1/NFPA 54 as "a space whose
volume is less than 50 cubic feet per 1000 Btu/hr (4.8
m3 per kW per hour) of the aggregate input rang of
all appliances installed in that space." A conned
space must have two combuson air openings. Size
the combuson air openings based on the BTU input
for all gas ulizaon equipment in the space and the
method by which combuson air is supplied:
Louvers and Grills
When sizing the permanent opening as illustrated in
Figure 1, consideraon must be taken for the design
of the louvers or grills to maintain the required free
area required for all gas ulizing equipment in the
space. If the free area of the louver or grill design is
not available, assume wood louvers will have 25%
free area and metal louvers or grills will have 75% free
area. Under no circumstance should the louver, grill
or screen have openings smaller than ¼”.
Example:
Wood: 10 in x 12 in x 0.25 = 30 in
2
Metal: 10 in x 12 in x 0.75 = 90 in
2
Locaon
To maintain proper circulaon of combuson air two
permanent openings (one upper, one lower) must be
posioned in conned spaces. The upper shall be
within 12 inches of the conned space and the lower
opening shall be within 12 inches of the boom of the
conned space. Openings must be posioned as to
never be obstructed.
Using Outdoor Air For Combuson
Outdoor air can be provided to a conned space
Combuson Air Requirements
Figure 1