Venng Requirements
Vent Dampers
Vent dampers must be cered in accordance with ANSI Z21.68
Before installing any ue damper, consult the local gas authority and damper manufacturer for proper
installaon.
Vent Inspecon
The enre vent system (Combuson air ducts, louvers etc., and exhaust vent) must be checked periodically for
signs of obstrucon or damage. If damaged components are observed they must be repaired or replaced
immediately.
Vent Size
This water heater is equipped with a 4” vent adapter and must never be aached to a vent smaller than 4”.
Certain applicaons may require vent diameters greater than 4” Consult your local gas supplier or authority to
aid in the proper vent diameter selecon per the requirements of the vent tables in the current edion of the
Naonal Fuel Gas Code ANSI Z223.1/NFPA 54.
Vent Connectors
Vent Connectors are relavely short runs of vent connecng the appliance to the chimney or vercal vent run.
Following is a list of appropriate vent connector material for use between the water heater and the chimney:
Type B (B-Vent) Double wall, U.L. listed vent pipe
Type B (B-Vent) Single wall, U.L. listed vent pipe
Note the following when installing a vent connector from the appliance to the chimney or vercal vent:
Length: A vent connector shall be as short as praccal and the appliance located as close as praccal to the
chimney or vent. The maximum horizontal length of the vent connector cannot exceed 75% of the
height of the chimney or vent. Unnecessary bends should be avoided as to not create excessive
resistance to ow of vent gases.
Prohibited locaons: Vent Connectors cannot pass through any ceiling, oor, rewall, or re paron.
CHIMNEY
OR
LISTED VENT
MIN. ¼ inch rise
per foot
Vent Connector
Single wall vent connectors: A single wall vent
connector must not pass through any interior
walls, oors or ceilings. A single wall vent
connector must not be installed in acs, crawl
spaces or any other conned space or inaccessible
locaon. Maintain a minimum of 6” from
combusbles when using single walled vent
connectors.
Double Walled, B-Vent: It is acceptable to pass
through walls or parons with double walled, B-
Vent.
Slope: Vent connectors must pitch ¼ inch per foot
(21mm per meter) upward.
WARNING
Thermal Operated Vent Dampers: Should NOT be used with this appliance. This appliance has a thermal ecien-
cy greater than 80%. This higher eciency will result in lower ue gas temperatures. Such temperatures may be
too low to acvate a thermal operated vent damper. Use of a thermal operated ue damper on this product may
result in spillage of exhaust gases and ulmately carbon monoxide poisoning.