User Guide
RH180 Manual 27
Final Checklist
□ The water heater is not exposed to corrosive
compounds in the air.
□ The water heater locaon complies with the
clearances.
□ The water supply does not contain chemicals or
exceed total hardness that will damage the heat
exchanger.
□ Ensure the water heater and its water lines are
protected from freezing. Damage due to freezing
is not covered by the warranty.
□ Conrm that the electricity is supplied from a 120
VAC, 60 Hz power source, is in a properly
grounded circuit, and turned on.
□ The installaon must conform with local codes or,
in the absence of local codes, with the Naonal
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the
Natural Gas and Propane Installaon Code, CSA
B149.1.
□ Verify proper clearances around the vents and air
intakes.
□ Ensure that the Combuson Air Requirements are
followed that will provide sucient combuson
air for the appliance.
□ Ensure you have used the correct venng
products for the model installed and that you
have completely followed the venng
manufacturer’s installaon instrucons and these
installaon instrucons.
□ The water heater must be vented vercally to the
outside of the building or structure.
□ Purge the water line of all debris. Debris will
damage the water heater. Use a bucket or hose
if necessary.
□ Ensure the water heater is vented in accordance
with Naonal Fuel Gas Code, ANSI Z223.1/NFPA
54 - latest edion and the requirements of state
or local codes.
□ Ensure that hot and cold water lines are not
crossed to the unit and are leak free.
□ Clean the inlet water lter by rst powering OFF
the water heater. Remove the lower enclosure.
Drain and relieve the pressure from the system.
Remove and clean the lter of any debris that
may reduce water ow. Once clean, replace the
lter. Close the drain valve and pressurize the
system. Power the unit back ON and set desired
temperature. For more informaon on cleaning
the lter please reference page 39 secon C.
□ Ensure that the temperature/pressure relief valve
is installed.
□ Check for proper water pressure to the water
heater. Minimum water pressure is 20 psi. Rinnai
recommends 30-50 psi for maximum
performance.
□ A manual gas control valve has been placed in the
gas line to the water heater.
□ Check the gas lines and connecons for leaks.
□ Conrm that the gas inlet pressure is within
limits.
□ Conrm that the water heater is rated for the gas
type supplied.
□ An extension cord or an adapter plug has not
been used with the water heater.
□ Verify the system is funconing correctly by
connecng your manometer to the gas pressure
test port on the water heater. Operate all gas
appliances in the home or facility at high re. The
inlet gas pressure at the water heater must not
drop below that listed on the rang plate.
□ Ensure the lower enclosure is installed.
□ Explain to the customer the importance of not
blocking the vent terminaon or air intake.
□ Explain to the customer the operaon of the
water heater, safety guidelines, maintenance, and
warranty.
□ Inform the consumer of the importance of good
water quality and its eects on the warranty.
□ Leave the enre manual taped to the water
heater, or give the enre manual directly to the
consumer.