Supplemental Manual
26
HE+ Series 1-Stage Supplemental Manual
-
(also see Heater Troubleshooting next page)
A. Miswired - check electrical supply (120Vac ± 5%)
B. Transformer bad (24Vac ± 10%)
C. Fuse/Circuit breaker bad
D. Bad control (check LED for steady on)
-
A. Miswired
B. Bad thermostat no voltage @ terminal W
C. Bad control (check LED for steady on)
--
A. Miswired (check PSW terminal voltage: 24Vac ± 10%)
B. Flame sense problem (existing flame: check LED - 2 flashes)
C. Bad control (check line voltage between L1 & IND)
A. Shorted electrode
B. Open HV cable
C. Bad control
A. Valve coil open
B. Open valve wire
C. Bad control (check 24Vac voltage between V1 & V2)
A. Bad electrode
B. Bad HV igniter wire
C. Poor ground at burner
D. Poor flame (check flame current)