Supplemental Manual
27
HE+ Series 1-Stage Supplemental Manual
(also see DSI Troubleshooting previous page)
-
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician.
SET THERMOSTAT TO CALL FOR HEAT
APPLY 120 VOLTS
• CHECK 120V TO DSI AT “L1”
• CHECK 120V OUT AT “IND” FROM DSI TO BLOWER
COMBUSTION AIR BLOWER STARTS
AIR PROVING SWITCH HAS CLOSED 24
VOLTS IS PRESENT AT “PSW” AT DSI
CONTROL.
• CHECK TUBING TO SWITCH IS CONNECTED AND
NOT BLOCKED OR KINKED
• CHECK AIR PRESSURE WITH MANOMETER
• CHECK FOR OBSTRUCTION IN THE AIR INTAKE
• REPLACE DEFECTIVE BLOWER
• CHECK INTEGRITY OF SWITCH
• REPLACE DEFECTIVE SWITCH
• CHECK DSI CONTROL FUSE FOR CONTINUITY
• VISIBLY CHECK IF IGNITER IS SHORTING OUT
• CHECK GROUND WIRING
• REMOVE AND INSPECT IGNITER AND LEAD
• CHECK BOOT OF THE IGNITION CABLE FOR SIGNS
OF MELTING OR OVERHEATING
• IF “YES” ... TAKE PROTECTIVE ACTION TO SHIELD
CABLE AND BOOT FROM EXCESSIVE TEMPERA-
TURE; REPLACE ANY DEFECTIVE COMPONENT
• CHECK CERAMIC INSULATOR AND CAP
• CHECK SPARK GAP SETTING IS 3/16” (ADJUST BY
MOVING THE GROUND PRONG ONLY)
• PERFORM IGNITION LEAD TEST (See SPARK IGNI-
TION CIRCUIT INSTRUCTIONS—Section 22)
• GOOD SPARK.....REPLACE IGNITER
• NO SPARK/OR WEAK.....REPLACE CONTROL
SPARK IGNITER / SENSOR
24V TO GAS VALVE
CONTINUED
NO
YES
YES
YES
NO
NO
• REMEDY 120 VOLTS SUPPLY FAULT
NO
NO
• FAULTY RELAY SWITCH IN DSI — REPLACE DSI
BLOCKED FLUE SWITCH IS CLOSED
24 VOLTS IS PRESENT AT “TH” AT DSI
CONTROL.
YES
NO
• CHECK TUBING TO SWITCH IS CONNECTED AND
NOT BLOCKED OR KINKED
• CHECK AIR PRESSURE WITH MANOMETER
• CHECK INTEGRITY OF SWITCH
• REPLACE DEFECTIVE SWITCH
• CHECK FOR AND REMEDY ANY OBSTRUCTION IN
THE VENT / TUBE