Engineering Specs

1
HVAC Guideline Specifications
HE+ Series (Single-stage, Two-stage & Modulating)
Positive Pressure Radiant Tube Type Gas-Fired Infrared Heater
Commercial/Industrial Applications
Part 1 General
1.01 SYSTEM DESCRIPTION
Indoor overhead mounted, electrically controlled positive pressure radiant tube type infrared heating
unit utilizing gas combustion for heating of spaces or areas.
1.02 QUALITY ASSURANCE
A. Heater will be tested in accordance with ANSI Z83.20-2016 / CSA 2.34-2016 Standards, and
certified by UL Laboratories of Canada
B. Each heater burner will be subjected to run testing on the assembly line.
C. The heater will be warranted by the manufacturer for defects in material and workmanship for a
period of three (3) years on the burner assembly and three (3) years on all other heater parts and
components.
1.03 DELIVERY, STORAGE, AND HANDLING
Heater will be stored to secure against damage and handled per manufacturer’s recommendations.
Part 2 Product
2.01 EQUIPMENT (STANDARD)
A. General:
Site assembled, modular infrared radiant heating unit for overhead mounted space or area heating
application. Supplied with the heater as required for field installation and start-up will be a burner
with all necessary factory installed wiring, piping, and controls and a radiant tube/reflector system,
complete with wire hangers, end-plate hanger and end plate, corresponding in length to the burner
input.
The radiant tube type infrared heating unit(s) will be manufactured by Rinnai.
Heater size(s) and capacity(s) are as noted on drawing and/or schedule
B. Emitting Tube System:
1. General:
a. All tubes will be 4 inch (100 mm) diameter with an emitting surface area of 152 in
2
(982
cm
2
) per linear foot (305 mm)
b. For inputs up to and including 205,000 Btuh (60.1kWh) the 10 foot (3050 mm)
combustion tube adjoining to the burner will be constructed of 16 gauge aluminized steel
c. For inputs greater than 205,000 Btuh (60.1kWh) the 10 foot (3050 mm) combustion tube
adjoining to the burner and the second emitter tube will be constructed of 16 gauge
stainless steel with a subsequent 10 foot (3050 mm) length of 16 gauge aluminized steel
d. The balance of the heat exchanger tube system (lengths as approved for burner input)
will be 10 ft (3050 mm) lengths of 16 gauge hot rolled steel
e. Hot rolled heat exchanger tubes will be coated with a high temperature emissive coating
f. The system tubes will have a swage of approximately 4 inches (100 mm) in length to
accommodate the connection of subsequent tubes and vent pipe at the heater
termination
g. Each tube connection in the system will be secured in place with a 4 inch (100 mm)
TorcTite® coupler