CONDENSATE DRAIN YES NO
If the condensate pump is installed, is it wired to deacvate the tankless water heaters in the event of
failure?
Did you verify the condensate drain pipe is as short as possible and has a downward pitch toward the drain
or condensate pump?
Is all condensate drained and disposed of as per local codes?
Did you use ONLY corrosion resistant materials for the condensate drain lines?
Did you verify the condensate drain pipe along its enre length is at least the same diameter as the drain
line (1/2 in. NPT)?
Did you check to ensure the condensaon drain lines are protected from freezing?
If a oor pump is not available or the drain is above the level of the condensate drain, did you install a
condensate pump?
Have you veried the condensate drain line is not plumbed with the pressure relief valve?
Have you conrmed the condensate drain line is not connected with an air condioning evaporator coil
drain?
Have you veried an external condensate trap is not installed?
Have you conrmed the end of the condensate drain pipe is open to atmosphere?
GAS SUPPLY YES NO
Did you verify the gas system is appropriately sized?
Did you verify each water heater is rated for the gas type supplied?
Have you performed a gas line and connecon leak test?
Is the inlet gas pressure within limits?
Did you purge the gas line of any debris before connecng the water heaters?
PRESSURE RELIEF VALVE (PRV) YES NO
Is the discharge from the PRV piped to the ground or into a drain system as per local codes?
Is the discharge line from the PRV pitched downward and does it terminate 6 in. (152 mm) above the
drains?
Is the discharge end of the line plain (unthreaded) and a minimum of 3/4 in. diameter?
Is the discharge line material suitable for at least 180° F water?
Did you take measures to protect the PRV and PRV discharge line from freezing?
Have you veried the PRV is not plumbed with the condensate drain line?
Have you veried the PRV is not plugged and that reducing ngs, valves, or other restricons are not
installed in the relief line?