Condensing Boiler RS100 Controller Training Program Training Program #501102A – 062311 www.rinnai.
Features and Benefits RS100 –Programmable Wall Thermostat with room setback • • • • • • • • The RS100 connects directly to the boiler and acts as a central thermostat for the entire structure Direct communication with the boiler allows it to fire based on the area’s immediate needs Operation is controlled by simple rotary push button technology Digital display (with backlight): • Fahrenheit or Celsius • Ability to display outdoor temperature • Ability to display supply temperature • Ability to display sy
Scope of Use Applications for the RS100 Room controller The RS100 is a room controller and not an on/off room thermostat. It is intended to work only with Rinnai boilers. When used in conjunction with a Rinnai boiler it will sense the room temperature and use it to influence the supply water temperature. This will allow less cycling of the boiler and a more efficient installation. The RS100 is designed to control a single circuit of heating.
Scope of UseSingle Zone System (RC mode) The RS100 can be used to control a single heating zone system. A single heating zone system has only one loop of heating. The placement of the RS100 is very important; it must be placed in the coldest room within the single zone system. If the RS100 is not placed in the coldest room there is a chance that the room will not receive enough heat and therefore not be comfortable. The RS100 needs no additional installer level programming to work for this installation.
Scope of UseMultiple Zone System (Outdoor Reset mode) If multiple zones are used, it is likely not beneficial to have a single zone controlling the boiler’s demand. The RS100 can be used where its room information does not influence the boiler’s demand. Its clock functions are still active as well as the ability to adjust a theoretical temperature for comfort.
Scope of UseMultiple Zone System (Outdoor Reset mode) Outdoor Sensor Zone Pump Piping Zone Thermostats Third Party Controller The boiler in this application is operating with constant circulation and no input from room thermostats (on/off) or third party controls. The third party control panel cannot be connected to the boiler with an RS100 also connected. Boiler thermostat terminals 22 and 23 are inactive when the RS100 is connected. www.rinnai.
INSTALLATION BASICS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.
Electrical Connections Below is the connection for the RS100. Please refer to the installation manual and Rinnai’s recommended application guide for more details or contact Rinnai’s Engineering Department as needed Release the tab at the bottom of the controller to access the connection points Connect the wires to the back panel of the controller. Ensure wire ―A‖ from the controller is connected to terminal 20 (wire ―A‖) on the Boiler. Ensure wire ―B‖ is connected to 21.
BASIC OPERATION THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.
RS100 Power-on Initialization RS100 – Display during initialization The following sequence will occur every time power is reset or the “reset” button on the boiler is pressed This process takes about 30 seconds A display test will occur where all characters are illuminated The selected language will display. “GB” = English The current software version will display (Version 2.3 is current as of 10/09) Auto set will display for a few seconds.
RS100 Navigation Overview After entering a chapter or display, any setting available to change will be flashing. A new setting can then be ―dialed in‖ Pressing the rotary button will save the new setting THR 26MAR ’09 8:05 69º Turning the dial will move to other settings that can be altered on that page Pressing the Information button will move to the previous page Continually pressing the information button will ultimately move back to the operation page www.rinnai.
RS100 Display Overview RS100 – Normal Operation Display Current heating mode 24 hour clock with status bar indicating operating times during current day (currently operating between 6-8 am and 4-10 pm) =daytime heating mode Day, Date, Month, Year (currently Monday, 22nd of August, 2005) =nighttime (setback) heating mode =summer switch off activated III Room or boiler (T1) operating temp in Celsius or Fahrenheit =frost protection activated I =If multiple time programs are enabled (P1-P3), this clock w
RS100 Operational Modes This allows selection of unique operational modes-a cursor is displayed above the selected mode. Any unique operating mode and its settings will be cancelled when a new unique mode is selected. Vacation mode-Heating will be inactive until the specified date (this example is September 24).At 0:00 (midnight) on this date, operation will resume. This can be set 250 days in advance. DHW operation is set to freeze protection (100°F default).
RS100 Operational Modes This allows selection of unique operational modes-a cursor is displayed above the selected mode. Any unique operating mode and its settings will be cancelled when a new unique mode is selected. DHW only will operate based on the times and temperatures set in the ―Timeprograms‖ chapter. If P1-P3 is selected, there will be up to three different schedules to choose. In this mode, heating will not operate—frost protection is enabled.
RS100 User Buttons Outdoor reset curve adjustment (K-Factor) 212 Default setting is 1.50 NOTE: If set to RC mode, adjusting this value will not have any effect on the controller or boiler. Example: If outdoor design temp is 14°F and max boiler supply is set to 122°F (perhaps for in-floor heating), a value of 1.00 should be entered here. 176 Boiler Temperature (F) This button adjusts the relation of boiler temperature to outside temperature.
RS100 User Buttons Information display Briefly pressing this button displays the following information (turning the dial clockwise will advance to the next reading): • Outside—displays current outside temperature reading from the outdoor reset sensor • Pressing the dial will show the average temperature over the last 24 hour period • Out.
RS100 User Buttons Daytime room temperature setting Briefly pressing this button displays current daytime area (room) set point. Turning the dial will adjust this value. The dial must then be pressed to enter the new value Nighttime room temperature setting Briefly pressing this button displays current nighttime area (room) set point. Turning the dial will adjust this value.
RS100 User Buttons-Shortcuts Pressing and holding the following buttons for three seconds will immediately display the following. Operational mode is changed back to Auto. Programmed timers will take effect Operational mode is changed to Party. A value will be displayed and available to change if needed. Operational mode is changed to Absent/Economy . A value will be displayed and available to change if needed.
USER AND INSTALLER SETTINGS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.
Parameter Access There are two levels of access for making parameter changes: • The user level allows clock and timer changes and basic system changes • To access this level, hold the rotary dial for approximately 3 seconds Hold the rotary dial for 3 seconds for consumer level parameter access • The installer level allows access for all pertinent parameters • To access this level, hold the heating and DHW buttons imultaneously for approximately 3 seconds • Code access will then display—using the dial to e
Parameter Chapters Once in the parameter menu, there are eight chapters that allow specific adjustments.
Time Programs • When entering the Time Program chapter, timers for only heating (HC) or only DHW (DHW) can be selected • Up to three events per day can be selected with a unique temperature (in Farhenheit or Celsius) • By default HC has one daily event from 6 am-10 pm • By default DHW has one daily event from 5 am-10 pm • Outside of these times, the setback temperature will be observed if no other events are added • By default HC will observe the nighttime outdoor reset curve or room setback temp of 61°F d
Time Programs-Copy Feature • After setting one day’s time events, they can be copied in several different ways: • From one day to another To copy: • Enter the ―TIMEPROGRAMS‖ • Select ―HC‖ or ―DHW‖ • From one day to Monday through Friday (1-5) • Dial the rotary button backwards (CCW) one click • The copy feature will be visible • From one day to Saturday and Sunday (6-7) • From one day to the entire week (1-7) www.rinnai.
Hydraulic Parameters • Hydraulic parameters should very rarely be adjusted • Hydraulic parameters are only available with the installer code (1234) PARA Description Range / Explanation OFF 2 DHW assignment 1 5 Disables DHW recognition (Any DHW features, info, etc will not display).
System Parameters • Some System parameters are accessible but should never be adjusted. This is indicated with N/A at the description.
System Parameters (continued) PARA Description 4 Summer setback temperature 5 9 10 System frost protect Climate Zone Building construction Range / Explanation OFF Factory Setting User Access 68°F Yes 37°F No 10°F No 1 No No summer setback System frost setting (Para 5) to 86°F When the outdoor sensor detects the selected temperature, the heating side of the boiler will not operate OFF No function -4°F to Summer setback (Para 4) When the outdoor sensor detects the selected temperatu
System Parameters (continued) PARA Description 11 Time to return to normal display 13 N/A Range / Explanation OFF 0.5 to 5 minutes OFF-ON Factory Setting User Access 2 minutes Yes OFF No No automatic return Time before controller will return to its normal operating screen (from point of no activity This should not be altered When entering this parameter, ―SET‖ will appear. Holding the dial for 5 seconds will cause the controller to re-initialize.
DHW Parameters • Some DHW parameters are accessible but should never be adjusted. This is indicated with N/A at the description.
Unmixed (HC) Circuit Parameters • Some HC parameters are accessible but should never be adjusted. This is indicated with N/A at the description. Ensure factory settings are always maintained at these parameters • HC parameters that are available at the user level are indicated below PARA 1 Description Type of reduced (night time setback) operation Range / Explanation ECO RED 2 Do not use 1.00-10.00 Economy-HC is off unless outdoor freezing temperature is detected.
Unmixed (HC) Circuit Parameters (continued) PARA 3 Description Controller application type (Outdoor reset or RC mode) Range / Explanation OFF Outdoor reset mode: The RS100 doesn’t use the room temp for operation. Boiler supply temp is displayed (pressing the dial displays room temp).
Unmixed (HC) Circuit Parameters (continued) PARA 6 8 Description Inrush optimization Room frost protection Range / Explanation OFF Not active 1-8 hours The amount of time the boiler will allow itself to operate before a heating event begins in order to be at the desired temperature of that event.
Unmixed (HC) Circuit Parameters (continued) PARA Description 12 Min. temp limit 50°F to max temp 13 Max. temp limit Min. temp to 176°F Factory Setting User Access Minimum boiler temperature limit in heating mode NOTE: This overrides Boiler Para 27 68°F No Maximum boiler temperature limit in heating mode.
Alarm Messages • The last 5 alarm messages can be viewed in the Alarm chapter. • The alarm number (1 through 5), the alarm code, date and time will display • During a live error or blocking code, the display will alternate between the code and the normal operating display Time (24 hour clock) Date (Oct 19, 2010) Code Number (see boiler install manual for code explanations) Error codes 1 through 5; 1 is the most recent E0=Error code B0=Blocking code www.rinnai.
Sensor Adjustment Chapter • Sensor adjustment allows an offset or calibration value to be applied to the RS100 • This is only accesible from the installer access level PARA Description 1 RS100 internal temperature sensor Range / Explanation -9 to +9°F Calibration value of the sensor www.rinnai.
Time Adjustment Chapter • Time adjustment allows date, day, and time for the RS100 • This is accesible from the user level (except Parameter 4) PARA Description Range / Explanation Factory Setting User Access 1 Time 0:00 to 23:59 NA Yes 2 Year 2001 to 2099 NA Yes 3 Day / Month 01.01 to 31.12 (dd/mm) ; The correct day will automatically display NA Yes OFF No 4 Automatic adjustment for Daylight Saving Time OFF / ON If set to ON, time will change the last Sunday in March and October.
BOILER PARAMETER SETTINGS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER’S INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.
Boiler Parameters (in relation to the RS100) • When using an RS100, the only adjustment that must be made at the boiler is PARA 73—most others can be made at the RS100 • Boiler parameter 2 or 14 may need to be set to establish an appropriate gradient control line (the defualt is 10°F/min) • When connecting an RS100, please observe the following notes at each parameter: Parameter Chapter PARA Default Range 1 176° 68 to176°F 2 00 5 Description RS100 Note Maximum supply temp in heating mode This wi
Boiler Parameters (in relation to the RS100) • When connecting an RS100, please observe the following notes at each parameter (continued): Parameter Chapter PARA Default Range Description 14 10°F/ min 028°F/min Gradient acceleration—this is set when para 2 is selected based on application or it can be set here This is not adjustable from the RS100 15 00 00 or 01 Booster after night reduction 00=no, 01=yes RS100 UC PARA 6 will override this setting 26° -4°F to 50°F Freeze protection activati
TROUBLESHOOTING THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.
Troubleshooting • When troubleshooting with an RS100, consider the following: • Jumping the thermostat terminals (22 and 23) to force the boiler to fire will do nothing unless the RS100 is disconnected from 20 and 21 • If the RS100 is not set for RC, the room conditions will not influence the boiler • If the RS100 is set for RC, outside temperature will not influence the boiler except for freezing or summer setback conditions • If max temp at the boiler is lower than the max temp at the RS100, the boiler’s
Thank You for being a part of Rinnai’s Product Expansion – RS100 Boiler Controller Training Program #501102A – 062311 www.rinnai.