Installation Guide
Rinnai Tankless Water Heater Installaon and Operaon Manual 29
Twin Pipe Terminaon Clearances
Direct Vent (Twin Pipe)
1
Combuson air and exhaust vent directly through separate
penetraons.
Twin Pipe Overview
Exhaust
Combuson
air
For illustraon purposes only. Listed equivalent length is based on worst case scenario of
3 X 90° elbows or 18 equivalent .
Twin Pipe Vercal Terminaon
of Mulple Water Heaters
Combuson air terminaon not permied in shaded area
Horizontal Vent and Combuson Air Piping
12 in. (0.30 m) above
grade or ancipated
snow level
12 in. (0.30 m) minimum
12 in. (0.30 m)
minimum
above
combuson
air opening
Roof
12 in. (0.30 m) above
grade or ancipated
snow level
12 in. (0.30 m)
minimum
Exhaust
Combuson
Air
Exhaust
Zone
60 in. (1.5 m)
minimum
12 in. (0.30 m)
minimum
Wall
Combuson
Air
Exhaust