Exhaust Vent Installaon Procedures:
• Aer ensuring the water heaters are mounted securely and
spaced 20.5” apart, install the appliance adapter on top of
the water heaters.
• Exhaust Venng is designed for a 3° rise. When the water
heaters are mounted at 20.5” spacing, the height increase is
1” per water heater. A 4” diameter extension pipe is
included with the kit that must be cut to length to account
for the rise from unit to unit. Aer cung, always deburr and
bevel the end of the vent piece so the sealing gaskets are not
damaged and operaon of the vent system is not
compromised.
• Install the elbows with hand cleanout cap to the 4” diameter
extension pipe. Do not cut or modify the elbow. Cleanout cap
should remain accessible for periodic inspecon and access
for service when needed.
• Aer combuson air and exhaust vent components are
appropriately posioned, securely fasten the “CVent
Appliance Adapter with Check Valve and Trap” to the top of
the water heater with a self tapping screw.
• Connect the combuson air opening of the appliance adapter
to one end of the ex connector and the other end of the ex
connector to the Combuson Air Collector.
• Connect the open end of the elbow to the exhaust header.
Securing Screw
Elbow
hand cleanout cap
4” Extension
Appliance
Adapter
Combustion Air Collector
Flex Connector
Elbow
Exhaust Collector