Installation Manual

Rinnai Tankless Rack System (TRS) Installation Manual 29
Rack Frame - Specifications
Frame Rail Type
Sheet Metal
Frame Material
Aluminum (0.090 5052-H32)
Frame Finish
Powder Coat
Color
Gray
Water & Gas Connections
Hot Water Trunk Line Diameter
2-1/2" 2”
Cold Water Trunk Line Diameter
2-1/2" 2”
Hot Water Trunk Line Material
Rigid Copper
Cold Water Trunk Line Material
Rigid Copper
Water Trunk Connection Type
2-1/2” PIPE 2” PIPE
Gas Trunk Line Diameter
1-1/2" 1-1/4”
Gas Trunk Connection Type
1-1/2” MNPT 1-1/4”MNPT
Gas Trunk Line Material Sch 40 Steel
Gas Branch Line Material PVC Over CSST
BTU and Flow Rates for CU199i, CU199e (NG/LP)
Number of Tankless Water Heaters 6 5 3 4 2
Flow rate @ 70°F rise (gpm) 32.4 27.0 16.2 21.6 10.8
Flow rate @ 100°F rise (gpm) 22.8 19.0 11.4 15.1 7.6
Minimum input rate (Btuh) 15,200
Maximum input rate (Btuh) 1,194,000 995,000 597,000 796,000 398,000
TRS06CU
TRS05CU
TRS03ILCU
Electric Requirements
Prewired Electrical Assembly N/A Yes (Indoor Models Only)
Voltage AC 120 Volts - 60 Hz
Max Current (Amperes) 24 20 16 12 12 8
TRS36CU
TRS46CU
TRS23ILCU
Condensate Trunk Line Diameter 3/4” N/A
Condensate Trunk Line Material Sch-40 PVC N/A
Condensate Trunk Connection Type 3/4” Pipe
N/A
6-Unit Free-Standing Frame (Connued)
Model
TRS06CU TRS05CU TRS46CU TRS36CU TRS03ILCU TRS23ILCU