Installation Manual
44  Rinnai Tankless Rack System (TRS) Installation Manual
1.  Locate the gang box on the side of the TRS frame. 
2.  Remove the 2 screws securing the front panel to the 
gang box. 
3.  Remove the front panel. 
4.  Run building-supplied electrical wiring and conduit to 
the gang box. 
5.  Connect building wiring to the 3 12AWG, THHN wires, 
Hot (Black), Neutral (White), and Ground (Green). 
6.  Reinstall the front panel to the gang box using 2 
screws. 
7.  When the building electrical power supply has been 
wired to the rack system, plug the indoor units into 
the outlet located under the center rack frame as 
shown on the next page. 
TRS04CU 
TRS36CU 
4 Unit Electrical 
Assembly with (2) 20 A, 
125 V, 2-Pole, 3 Wire 
Grounding Receptacles 
Electrical Assemblies are installed on the middle rack 
frame of the following indoor racks for single point 
electrical connection. 
Refer to the Specifications sections in this manual 
for electrical requirements.  
Conduit 
Punch-out 
Green (Ground) 
Black (Hot) 
White 
(Neutral) 
 WARNING 
Shut o building supply power prior to connecng to 
TRS electrical assembly. Failure to do so may result 
in property damage, bodily harm, or death.  
TRS03ILCU 
TRS03CU 
TRS46CU 
6-Unit Electrical 
Assembly with (3) 20 A, 
125 V, 2-Pole, 3 Wire 
Grounding Receptacles 
TRS05CU 
TRS06CU 
Pre-Wired Electrical Assembly 
Instrucons 
Interior Models Available 
with Electrical Assemblies 