Installation Manual

Rinnai Tankless Rack System (TRS) Installation Manual 35
THE WALL MUST BE CABABLE OF CARRYING THE OPERATING WEIGHT OF THE
INSTALLED TRS SYSTEM. CONSULT A STRUCTURAL ENGINEER FOR STRUCTURAL
ANALYSIS OF THE WALL AND APPROPRIATE HANGING METHODS BEFORE ATTEMPTING TO HANG THE
TRS SYSTEM. FAILURE TO COMPLY WITH THE ABOVE REQUIREMENT COULD RESULT IN SUBSTANTIAL
PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
Idenfy the installaon locaon and conrm that the installaon will meet all required clearances.
In the event of a conict or inconsistency between items indicated in this manual regarding code requirements,
the more stringent standard shall prevail.
Corner-hanging rack models include the TRC02CU.
Using the holes in the wall hanging brackets,
securely aach the brackets level to the wall.
Ensure that the aachment strength is
sucient. Brackets are to be installed within
1/2” from the corner.
Li the corner hanging rack and insert the top
of the frame into the two brackets.
Secure the frame to the hanging brackets using
two 12-14 thread, 2-1/2” long drill point screws
(supplied). Fastener head is 5/16” hex.
WARNING
Secure Corner-Hanging Racks (TRC Models)
1
2
3
Instrucons