Installation Manual
54  Rinnai Tankless Rack System (TRS) Installation Manual
SETTING 
#  
SETTING              
DESCRIPTION  
SELECTION  
A 
c 
E  F 
08  Cascade  Secondary (1-23)  Primary         
09 
Units in Standby 
(Cascade) 
1  2  3  4  5  6 
Parameter Sengs (Cascade Communicaon) 
Refer to the Parameter Seng secon of the “Rinnai Tankless Water Heater Installaon and Operaon Manual” for 
instrucons on accessing and changing parameter sengs. 
Seng Secondary ID 
Aer idenfying the “Primary” water heater in the 
parameter sengs, set the Secondary ID for all re-
maining water heater in the system by pressing the 
“On/O” buon on the controller. 
When ID seng is successful, the controller display 
will change from “- - -” to the newly set ID number. 
140 
-01 
-02 
-03 
Secondary 01 
Primary Water 
Heater 
Secondary 02  Secondary 03 
Idenfy Secondary ID by pressing 
“On/O”  
08 Cascade: 
    Primary: Select the water heater intended to be the Primary water heater for cascade communicaon. Set the 
parameter seng for this water heater to “Primary” (08 ).  
        NOTE: Controller will display the set temperature for the system.      
    Secondary: Factory Default seng for each water heater is set to “Secondary”. Parameter adjustment is only 
needed on the water heater idened as “Primary”. 
        NOTE: Controller will display “- - -”.  
09 Units in Standby:  
    Adjust the parameter seng of the primary unit to set the number of water heaters in standby. Standby units will 
maintain operaon with the water ow control valve in the open posion. The remaining water heaters will 
maintain the water ow control valve in the closed posion. 
Programming Cascade Communicaon 