Installation Sheet

15 Rinnai Rack Installation
MSB InstallaƟon
All of the water heaters should be electronically con
nected using the MSB control system. The only excep
on is when a water heater is dedicated to recovering a
tank. The MSB kits can electronically connect up to 25
water heaters.
When over 5 water heaters are connected together,
MSBM units are connected using MSBC2 kits.
If mulple MSBM are used, then at least three water
heaters should be connected to each MSBM. Example:
With 7 water heaters, one MSBM should control 4 wa
ter heaters and the other MSBM should control 3 wa
ter heaters.
The temperature seng for all of the connected water
heaters is controlled by the temperature controller
connected to the water heater with the master MSB
Board. Temperature controllers connected to the other
units will provide maintenance codes for their respec
ve units.
On applicable models a single MCC91 can be connect
ed to the master MSB Board to provide temperatures
greater than 140ºF for all the water heaters in the MSB
system.
M MSB-M control board
A Connector cable A (part of MSB-M kit; replace
with MSB-C3 cables for V Series)
C1 MSB-C1 cable (9.8 feet) for connecting water
heaters within a banked system (up to 5), (use
MSB-C3 cables for V Series)
C2 MSB-C2 cable (13.1 feet) for connecting MSB-M
control boards (up to 5)
In the diagram above, 25 water heaters are
electronically connected. Each bank of 5 is controlled
by an MSBM control board. These boards are
connected to each other with MSBC2 cables. One
MSBM is the controlling or master MSBM for the
enre system.
M
A
C2
C1
Water Heater
PC board