Installation Sheet

9 Rinnai Rack Installation
MounƟng Wall Racks
1. Idenfy the installaon locaon and conrm that the installaon will meet all required clearances.
2. Securely aach the rack to the wall. Ensure that the aachment strength is sucient to support the weight.
Refer to the weight in the Specicaons secon.
Use a leveling tool to ensure that the water heater is level. Proper operaon requires that the water heater
be level. The rack / water heaters should be installed in an upright posion. Do not install upside down or
on its side.
Securing Free Standing Racks
28.50
26.50
53.09
0.563
(4) Plcs
55.11
26.50
28.50
36.53
34.51
0.563
(4) Plcs
1. Use 41/2” HILTI KBTZ expansion anchors or approved equivalent. Minimum embedment (hef) = 3.25”.
Minimum concrete thickness to be 6”.
2. All mechanical components shall be anchored and installed per the notes in this manual. Where no detail is
indicated, anchorage of equipment to building structure shall be in accordance to the applicable naonal
and/or local codes having jurisdicon.
3. The size and embedment specied are for anchors installed in stone or aggregate concrete only, for other
anchorage details the contractor or engineer on record for the building shall consult with a licensed struc
tural engineer for all anchorage of equipment not called out in this manual.
4. In the event of a conict or inconsistency between items indicated in this manual with code requirements,
the more stringent standard shall prevail.
Boom view of
free standing