The two controller variants for operational reliability offer a
comprehensive range of functions. Essential control elec-
tronics are well protected and cooled in the inner circuit.
Both variants have the following properties:
Three voltage options: 115 V, 230 V, 400/460 V 3
˜
Integral start-up delay and door limit switch function
Icing protection function
Monitoring of all motors
Phase monitoring for three-phase units
Basic controller:
Visualisation of the operating status via LED display:
− Voltage applied, functions OK
− Door open
− Overtemperature
− High-pressure monitor has switched
Switching hysteresis: 5 K
Floating fault signal contact in case of overtemperature
Setpoint adjustable from outside via potentiometer
(setting range 20 – 55 °C)
Intelligent control
e-Comfort controller:
Master/slave function for up to 10 units, i.e. the unit which
reaches the setpoint first reports this to the “master unit”
which switches all other “slave units” on and off. The unit
which activates the door limit switch function reports this
to the “master unit”, which switches off all ”slave units“.
Switching hysteresis: 2 – 10 K; preset to 5 K
System alarm, individually configurable for 2 floating fault
signal contacts
Visualisation of the current enclosure internal temperature
and all system messages on the display
Storage of all system statuses in the log file
Optional interface card (SK 3124.200) with RS-232,
RS-485, RS-422 and PLC interface for integration into
superordinate remote control systems, e.g. with CMC,
is also possible