Data Sheet

Technical System Catalogue/Climate control
Sample calculation
3 - 66
Step 1: Raise the water inlet temperature
The temperature in the cold aisle is precisely definable and
identical throughout, thanks to optimised temperature
distribution.
Increasing the air intake temperature also increases
the waste air temperature.
Increasing the air intake temperature improves the
performance of free cooling.
Possible energy saving in the production of chilled
water: up to 26%.
Q
total
(Q
sens.
) 80 kW (80 kW) – 79.9 kW (79.9 kW)
T
air; hot
(rel. humidity) 26 °C (45%) – 31 °C (32%)
T
air; cold
(rel. humidity) 15 °C (89%) – 19.8 °C (62.2%)
T
water; inlet
10 °C – 15 °C
T
water; return
15 °C – 20 °C
P
electr.
for cold water 190 MWh/a – 139 MWh/a
–26%
Step 2: Reduce the volumetric air flow
For a constant air volume flow rate, the cooling output
improves with airside temperature difference.
By reducing the volumetric air flow, the return waste air
temperature is increased,
Possible energy saving in the operation of the fans:
up to 60%.
Q
total
(Q
sens.
) 79.9 kW (79.9 kW) – 88.4 kW (88.4 kW)
T
air; hot
(rel. humidity) 31 °C (32%) – 36 °C (25%)
T
air; cold
(rel. humidity) 19.8 °C (62.2%) – 19.7 °C (64.6%)
V
air
(ext. press.) 22000 m
3
/h (80 Pa) – 17000 m
3
/h (20 Pa)
P
electr.
for CRAC fan 3.6 kW – 1.5 kW
–60%
Step 3: Reduce the throughput
The speed of the pump may be reduced because a smaller
amount of cooling water is required to provide the same
cooling output if the return water temperature is increased.
Possible energy saving in the operation of the pump:
up to 14%.
Potential saving in the production of chilled water:
up to 17%.
Q
total
(Q
sens.
) 88.4 kW (88.4 kW) – 80 kW (80 kW)
T
air; hot
(rel. humidity) 36 °C (25%) – 36 °C (25%)
T
air; cold
(rel. humidity) 19.7 °C (64.6%) – 21.3 °C (54.2%)
T
water; inlet
15 °C – 15 °C
T
water; return
20.6 °C – 23.5 °C
V
water
(P
electr.
) 13.6 m
3
/h (3 kW) – 8.1 m
3
/h (2.3 kW)
P
electr.
for cold water 143 MWh/a – 125 MWh/a
–17%
Summary
Energy saving:
Fans: 19 MWh/a
Pumps: 6 MWh/a
Cold water production: 65 MWh/a
Overall: 90 MWh/a
Cost saving with Rittal aisle containment:
up to 36%.
Q
total
(Q
sens.
) 80 kW (80 kW) – 80 kW (80 kW)
T
air; hot
(rel. humidity) 26 °C (45%) – 36 °C (25%)
T
air; cold
(rel. humidity) 15 °C (89%) – 21.3 °C (54.2%)
V
air
(ext. press.) 22000 m³/h (80 Pa) – 17000 m³/h (20 Pa)
T
water; inlet
10 °C – 15 °C
T
water; return
15 °C – 23.5 °C
V
water
(P
electr.
) 13.8 m
3
/h (3 kW) – 8.09 m
3
/h (2.3 kW)
P
electr.
for CRAC fan 3.6 kW – 1.5 kW
P
electr.
for cold water 190 MWh/a – 125 MWh/a
P
electr.
Total 248 MWh/a – 158 MWh/a
–36%