Data Sheet
Technical System Catalogue/Climate control
Liquid Cooling Package
3 - 71
Rack climate control
The LCP for rack climate control is designed for siting
within a bayed enclosure suite. The cold air is expelled
sideways on the front of the servers, and warm air is
drawn back in at the rear. The LCP for rack climate con-
trol is ideal for maximum cooling performance and maxi-
mum fail-safeness, thanks to redundancy of all key com-
ponents.
A large-scale high-capacity air/water heat exchanger,
designed as the rear door of the server enclosure,
ensures that heated waste air from the servers is cooled
down to server intake air level. This is achieved extremely
energy-efficiently, because no electrical power is required
for fans. High inlet temperatures above the dew point
improve energy efficiency still further.
Technology
CW = Chilled Water
T3+ = for Tier 3
CW T3+ CW CW
Output kW
10, 20, 30,
40, 50, 60
25 20
Cooling medium Water Water Water
Auto-load balancing – –
Auto-recovery – –