User manual
5 Installation
EN
16 Rittal enclosure cooling unit
Loosen the four threaded bolts in the corners of the
cover which connect the cover to the chassis.
Carefully pull the cover forwards (approx. 5 cm) from
the chassis.
The PE conductor connection between the cover and
the chassis is located on the right-hand side, approx-
imately halfway up.
Fig. 20: PE conductor connection (viewed from behind)
Key
1 PE conductor connection, cover
2 PE conductor connection, chassis
Pull the flat-pin connector of the PE conductor off in-
wards, preferable on the chassis.
Remove the cover completely from the chassis, and
place or lay it down somewhere safe.
There is a clip prefitted to the top edge of the chassis
on the front. This clip will later prevent the chassis from
falling out of the mounting cut-out before it is properly
secured with the threaded bolt.
Fig. 21: Clip on the top edge of the chassis
Key
1Chassis
2 Clip in chassis
3 Seal
Lift up the chassis, preferably with a lifting eye using
suitable lifting gear, and insert it into the mounting cut-
out in the door or side panel of the enclosure from the
inside with the edge fold at the bottom of the chassis.
If transportation by crane is not possible, lift the chas-
sis into the mounting cut-out in the same way using
the handle.
Fig. 22: Edge fold at bottom of chassis
Key
1 Edge fold on chassis (towards cover)
2 Outside of enclosure door
Push the chassis into the mounting cut-out at the top
until the clip behind the cut-out latches home.
Caution!
The cooling unit will only be stable as
long as the cover and chassis are con-
nected. For this reason, be sure to brace
the chassis, in particular, to prevent it
from falling over before removing the
cover.